Skip to product information
1 of 2

🚀 Genuine products, vast inventory, swift shipping!

NAIO-03 64212389 ABB Analog I/O Extension Module

NAIO-03 64212389 ABB Analog I/O Extension Module

Technical Specifications:

Manufacturer:
ABB
Product No.:
NAIO-03
Condition:
In Stock
Product Type:
I/O Extension Module
Product Origin:
SE
Weight:
300g
Shipping port:
Xiamen
Warranty:
12 months

🌟 Technical Specifications

Parameter Specification
Product ID 64212389
🔋 Power Supply 24 VDC
⚡ Power Consumption 3 Watts
⚖️ Weight 0.3 kg
📏 Dimensions 45 mm x 75 mm x 105 mm
🔒 Protection Rating IP 20
🔧 Installation Mountable on standard DIN rail
Input Features
  • ±0(4) to 20 mA
  • ±0(2) to 10 V
  • ±0 to 2 V
🔍 Input Impedance
  • 100 Ω (current)
  • 200 kΩ (voltage)
📊 Resolution
  • Unipolar mode: 0.024% (12-bit)
  • Bipolar mode: 0.048% (11-bit + sign bit)
📏 Accuracy ±0.5% at full scale at 25°C
🌡️ Temperature Coefficient ±100 ppm/°C
⚡ Common Mode Voltage +15 V
📤 Output Features
  • Output Signal Type: 0(4) to 20 mA
  • Maximum Load Impedance: 700 Ω
  • Resolution: 0.024% (12-bit)
  • Accuracy: ±0.5% at full scale at 25°C
  • Temperature Coefficient: ±100 ppm/°C
🔗 Connectivity and Configuration
  • Optical transmitter and receiver (Hewlett-Packard universal connector) for ACS 600 connection
  • Two terminal blocks (Phoenix Contact MVBSTW 2.5/8-ST-5.08) for analog I/O signal and power connections
  • Wire Cross-Section Area: 0.5 to 2.5 mm²
📜 DIP Switches
  • Six DIP switches for node address configuration (default: 5, max: 63)
  • One DIP switch for selecting between bipolar and unipolar modes
  • Four DIP switches for choosing input signal types
🌍 Environmental Conditions
  • Operating Temperature: 0 to +50°C
  • Relative Humidity: 5% to 95%, non-condensing (max 60% with corrosive gases)
  • Pollution Degree: Chemical gases (IEC 721-3-3, level 3C2), Solid dust (IEC 721-3-3, level 3S2)
  • Installation Height: Up to 2000 m above sea level (contact ABB for higher altitudes)
📈 General Performance
  • Current Consumption: 160 mA at 24 VDC
  • Insulation: Isolated from power and ground
  • Test Voltage: 1.5 kV AC for 1 minute
  • Fast Transient Immunity: 4 kV (IEC 801-4)
  • Electromagnetic Radiation Compliance: EN 55022 B
⏲️ Additional Features Hardware Filtering Time: Approximately 2 ms

Related Tags :

View full details