🚀 Genuine products, vast inventory, swift shipping!
MTL MTL4516 | Switch / Proximity Detector Interface
MTL MTL4516 | Switch / Proximity Detector Interface
Technical Specifications:
Manufacturer:
MTL
Product No.:
MTL4516
Condition:
In Stock
Product Type:
Switch / Proximity Detector Interface
Product Origin:
USA
Weight:
200g
Shipping port:
Xiamen
Warranty:
12 months
MTL Product Information |
|
---|---|
Product Type: | MTL4516 , MTL4516C |
MTL Specification |
|
---|---|
Number of Channels: | Two |
Location of Switches: | Zone 0, IIC, T6 hazardous area Div. 1, Group A hazardous location |
Location of Proximity Detector: | Zone 0, IIC, T4–6 hazardous area if suitably certified Div. 1, Group A hazardous location |
MTL Hazardous-Area Inputs |
|
---|---|
Compliance: | Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR) |
Voltage Applied to Sensor: | 7 to 9V DC from 1kΩ ±10% |
MTL Input/Output Characteristics |
|
---|---|
Normal Phase: | Outputs closed if input > 2.1mA (< 2kΩ in input circuit) Outputs open if input < 1.2mA (> 10kΩ in input circuit) Hysteresis: 200µA (650Ω) nominal |
Line Fault Detection (LFD): | User-selectable via switches on the side of the unit. Open-circuit alarm on if Iin < 50µA Open-circuit alarm off if Iin > 250µA Short-circuit alarm on if Rin < 100Ω Short-circuit alarm off if Rin > 360Ω Note: Resistors must be fitted when using the LFD facility with a contact input 500Ω to 1kΩ in series with switch 20kΩ to 25kΩ in parallel with switch |
MTL Safe-Area Output |
|
---|---|
Relay Characteristics: | MTL4516/C: Response time: 10ms maximum Contact rating (Safe Area): 10W, 0.5A, 35V DC Contact rating (Zone 2): 10W, 0.5A, 35V DC |
MTL5516C: | Response time: 10ms maximum Contact rating (Safe Area): 250V AC, 2A, cosØ >0.7, 40V DC, 2A, resistive load Contact rating (Zone 2): 35V, 2A, 100VA. |
Maximum Current Consumption: | 35mA at 24V |
Power Dissipation within Unit: | 0.84W at 24V |
MTL Safety Description |
|
---|---|
Terminals 2 to 1 and 3: | Uo=28V Io=93mA Po=651mW Um = 253V rms or DC |
Terminals 1 to 3: | Simple apparatus ≤1.5V, ≤0.1A and ≤25mW; can be connected without further certification into any IS loop with an open-circuit voltage <28V |