Technical Specifications:

Manufacturer:
Honeywell
Product No.:
FC-DCOM-232/485
Condition:
In Stock
Product Type:
RS232/485 Communication interface FTA
Product Origin:
USA
Weight:
500g
Shipping port:
Xiamen
Warranty:
12 months

Description

The Honeywell FTA FC-DCOM-232/485 is a combined RS232/RS485 communication interface for the Safety Manager. It provides connectivity via RS485/422 or RS232.

  • Power Supply: Powered by connected Control Processor(s), eliminating the need for separate supply wiring.
  • Grounding: Requires connection to earth to shield internal cables and field connector housings.
  • Installation: Universal snap-in design for standard DIN EN rails.

Cable Lengths

The maximum cable length for RS232, RS422, and RS485 communication varies based on baud rate and communication method (full-duplex or half-duplex):

Communication Method Baud Rate Maximum Cable Length
RS232 (full-duplex) ≤ 100 kBd 10 m
RS422 (full-duplex) ≤ 100 kBd 1.2 km
RS485 (full-duplex) ≤ 100 kBd 1.2 km
RS485 (full-duplex) ≤ 125 kBd 1 km
RS485 (full-duplex) ≤ 1 MBd 120 m
RS485 (full-duplex) ≤ 2 MBd 60 m
RS485 (half-duplex) ≤ 100 kBd 600 m
RS485 (half-duplex) ≤ 125 kBd 500 m
RS485 (half-duplex) ≤ 1 MBd 60 m
RS485 (half-duplex) ≤ 2 MBd 30 m

Technical Data

  • Model Numbers:

    • FS-DCOM-232/485 V2.1
    • FC-DCOM-232/485 V2.1
    • Note: Conformal coating indicated by “CC” in version numbers.
  • Approvals: CE, TUV, UL, FM

Physical Specifications

  • Module Dimensions: 110 × 70 × 61 mm (4.33 × 2.76 × 2.40 in)
  • Terminal Dimensions: 6 × 57 × 47 mm (0.24 × 2.24 × 1.85 in)
  • DIN Rail Compatibility: TS32 / TS35 × 7.5
  • Used Rail Length: 117 mm (4.6 in)

Power Requirements

  • Input Voltage: 5 VDC ±5%
  • Input Current: Max 500 mA, supplied by Control Processor(s)

Output Specifications

  • RS232 Output: According to EIA/TIA-232 levels
  • RS232 Baud Rate: 0—250 kBaud
  • RS485/422 Output: According to EIA/TIA-485-A levels
  • RS485/422 Baud Rate: 0—2 MBaud (supports transparent, FM0, FM1, or Manchester coded communication)