HIMA HIMatrix F60 DI 32 01 Safety-Rated Digital input Module
HIMA HIMatrix F60 DI 32 01 Safety-Rated Digital input Module
Technical Specifications:
Manufacturer:
HIMA
Product No.:
F60DI3201
Condition:
In Stock
Product Type:
Digital input Module
Product Origin:
DE
Weight:
1400g
Shipping port:
Xiamen
Warranty:
12 months
Product Description
HIMA HIMatrix F60 DI 32 01 (F60DI3201) is a module featuring 32 digital inputs designed for the modular F60 system. It is suitable for safety-related applications, certified by TÜV for up to SIL 3 according to IEC 61508, IEC 61511, IEC 62061, Cat. 4 and PL e according to EN ISO 13849-1, and SIL 4 according to EN 50126, EN 50128, and EN 50129.
Key Features:
- 32 digital inputs
- Inputs are galvanically separated to the I/O bus
- Can be inserted in the F60 subrack's slots 3 to 8 (slots 1 and 2 reserved for power supply and central modules)
- Equipped with safety-related inputs divided into 4 groups of 7 inputs and 1 group of 4 inputs
- Capable of line control for detecting short-circuits or open-circuits on emergency stop inputs
- Error handling includes triggering the ERR LED and processing a low-level signal in the event of a fault
Technical Specifications
General:
- Operating Voltage: 24 VDC, -15% to +20%, ripple < 15%, from a power supply unit with safe insulation according to IEC 61131-2
- Operating Data: 3.3 VDC / 0.05 A, 24 VDC / 0.2 A
- Ambient Temperature: 0°C to +60°C
- Storage Temperature: -40°C to +85°C
- Protection Class: III (IEC/EN 61131-2)
- Pollution Degree: II (IEC/EN 61131-2)
- Altitude: < 2000 m
- Housing: Standard IP20
- Space Requirement: 6 RU, 4 HP
- Weight: 260 g
Digital Inputs:
- Input Voltage: Nominal 24 VDC
- Input Current: Approximately 7 mA per channel
- Input Delay: 5 ms
- Debouncing Time: Configurable, typically 0 to 25 ms
- Line Control: Supports line control for emergency stop applications according to EN ISO 13849-1
Safety Functions:
- Safety Standards: IEC 61508 (SIL 3), IEC 61511, IEC 62061, EN ISO 13849-1 (Cat. 4, PL e), EN 50126, EN 50128, EN 50129 (SIL 4)
- Fault Detection: Fault detection mechanisms include line control for detecting short-circuits or open-circuits, ERR LED indication, and error code generation for user program handling
Certification:
- TÜV Certification: Certified for safety-related applications up to SIL 3 and SIL 4
- Conformity Marks: CE, other relevant conformity marks
Environmental Requirements:
- Operating Temperature: -25°C to +70°C for DI 32 014 variant
- Vibration and Shock: Tested according to EN 50125-3, EN 50155 (class 1B according to IEC 61373)
Status Indicators:
- RUN LED (Green): Indicates operating voltage presence
- ERR LED (Red): Indicates module or external faults
- I/O LEDs (Yellow): Indicate the activity status of each channel
Equipment, Scope of Delivery:
- DI 32 01: Standard module with 32 digital inputs
- DI 32 014: Enhanced module with extended temperature range, vibration and shock resistance
Connection and Installation:
- Mounting: In F60 subrack slots 3 to 8
- Wiring: Ensure proper connection to avoid cross-circuits, improper connections, and earth faults
- ESD Protection: Follow ESD protective measures to avoid damage
For detailed instructions on installation, configuration, and operation, refer to the relevant sections of the HIMatrix system manuals and safety manuals.