Skip to product information
1 of 3

🚀 Genuine products, vast inventory, swift shipping!

HIMA F3331 F 3331 8 fold output module, testable safety related

HIMA F3331 F 3331 8 fold output module, testable safety related

Technical Specifications:

Manufacturer:
HIMA
Product No.:
F3331
Condition:
In Stock
Product Type:
Output Module
Product Origin:
DE
Weight:
2000g
Shipping port:
Xiamen
Warranty:
12 months

Module Type: HIMA F3331

General Specifications:

  • Number of Channels: 8
  • Output Type: Digital
  • Safety Rating: Safety-related (suitable for applications with safety requirements)
  • Requirement Class: AK 1 to AK 6

Output Ratings:

  • Current Rating:
    • Per Channel: 500 mA
    • Short Circuit Current: 0.75 to 1.5 A (module can handle temporary short circuits)
  • Voltage Rating: Likely 24 VDC (typical for similar modules)
  • Load Types:
    • Resistive, Inductive: Up to 500 mA (12 W)
    • Lamp: Up to 4 W

Safety and Functional Features:

  • Integrated Safety Shutdown
  • Safe Isolation
  • Line Monitoring
  • Output Signal on L-Loss: No (outputs won't activate if L+ power supply is interrupted)

Automatic Testing:

  • Module is automatically tested during operation.
  • Main test routines include:
    • Reading back of output signals. Operating point for 0 signal read back is ≤ 6.5 V.
    • Switching capability of test signals and cross-talk (walking-bit test).
    • Line monitoring.

Additional Specifications:

  • Outputs are short circuit proof up to 500 mA.
  • Internal Voltage Drop: Maximum 2 V at 500 mA load.
  • Admissible Line Resistance (in + out): Maximum 11 Ohms.
  • Undervoltage Tripping: Activates at ≤ 16 V.
  • Output Leakage Current: Maximum 350 µA.
  • Maximum Output Voltage if Reset: 1.5 V.
  • Current Input for Watchdog: Maximum 30 mA.
  • Duration of Test Signal: Maximum 200 µs.
  • Space Requirement: 4 TE (standard unit in a rack system)

Power Consumption:

  • 5 V DC: 130 mA
  • 24 V DC: 180 mA (additional load)

Application: Suitable for safety-critical applications requiring reliable digital output control with integrated safety features and automatic testing capabilities. Ideal for industrial automation environments where adherence to safety standards is crucial.

Related Tags :

View full details