Technical Specifications:

Manufacturer:
HIMA
Product No.:
F6705
Condition:
In Stock
Product Type:
Digital-To-Analog Converter Module
Product Origin:
DE
Weight:
1200g
Shipping port:
Xiamen
Warranty:
12 months

Description:

The HIMA F 6705 is a 2-fold digital-to-analog converter module designed for safety-related applications. It provides outputs of 0/4 ... 20 mA, which are individually galvanically isolated. The module features safety isolation and an integrated safety shutdown, and can operate in either source or sink mode. It meets requirement class AK 1 ... 6 and is automatically fully tested during operation.

Technical Specifications:

  • Outputs:
    • Current Output: 0/4 ... 20 mA
    • Resolution: 12 bits (4095 steps); 0 = 0 mA, 3840 = 20 mA
  • Burden (RB):
    • Source Mode: ≤ 550 Ohm including line resistance to the burden
    • Sink Mode: ≤ (UQ - 10 V) / 21.2 mA (UQ = source voltage)
  • Errors:
    • Basic Error: ≤ 0.2% (40 µA) at 25 °C
    • Operating Error: ≤ 0.4% at 0 ... +60 °C
  • Line Length: Maximum 1000 m (consider burden)
  • Electric Strength: 250 V against Analog-GND
  • Basic Status with Plug-in: I ≤ 40 µA
  • Source Voltage (UQ) for Sink Mode: 10 ... 30 V
  • Space Requirement: 4 TE
  • Operating Data:
    • 5 V DC: 85 mA
    • 24 V DC: 130 mA

Additional Features:

  • Automatic Testing:
    • Linearity of the DA-converter
    • Cross-talk between the outputs
    • Safety shutdown
  • Cable Specifications:
    • Cable Type: LiYCY
    • Dimensions: 8 x 0.5 mm², l = 120 mm, q = 2.5 mm²
    • Channel Connection Color Coding: Specific colors assigned for each channel.
    • Flat Pin Plug: 2.8 x 0.8 mm², 6.3 x 0.8 mm for the cable screen, to be connected to the earth bar under the slot.
  • Redundant Current Connection:
    • Total current to the burden (RB) is the sum of individual currents.
    • Admissible burden resistance is halved in redundant mode.
    • Paralleled channels must operate in the same mode (source or sink).
    • Each output channel should generate half of the total current to balance load and minimize temperature error.
  • Bipolar Current Connection:
    • Supports output of currents between -20 mA to +20 mA.
    • Total current is the sum of individual currents (IG1 = I11 - I21 or IG2 = I12 - I22).
    • Positive and negative parts of the current are generated by different modules for accuracy.

Operational Notes:

  • Unused channels must be terminated with a jumper to prevent module error messages.
  • Ensure proper programming in the user’s program to manage the operation mode and current generation accurately.