Skip to product information
NaN of -Infinity

🚀 Genuine products, vast inventory, swift shipping!

Digital Output Module | 6ES7222-1HH32-0XB0 Siemens

Digital Output Module | 6ES7222-1HH32-0XB0 Siemens

Technical Specifications:

Manufacturer:
Siemens
Product No.:
6ES7222-1HH32-0XB0
Condition:
In Stock
Product Type:
Digital Output Module
Product Origin:
DE
Weight:
260g
Shipping port:
Xiamen
Warranty:
12 months

Siemens Product Information

Article Number (Market Facing Number): 6ES7222-1HH32-0XB0

Siemens Supply Voltage

Permissible Range, Lower Limit (DC): 20.4 V
Permissible Range, Upper Limit (DC): 28.8 V

Siemens Input Current

From Backplane Bus 5 V DC, Max.: 135 mA
From Load Voltage L+ (Without Load), Max.: 11 mA/relay coil

Siemens Power Loss

Power Loss, Typ.: 8.5 W

Siemens Digital Outputs

Number of Digital Outputs: 16
In Groups Of: 1
Short-Circuit Protection: No; to be provided externally
Switching Capacity of the Outputs: With resistive load, max.: 2 A
On lamp load, max.: 30 W with DC, 200 W with AC
Output Voltage: Rated value (AC): 5 V AC to 250 V AC
Rated value (DC): 5 V DC to 30 V DC
Output Current: For signal "1" permissible range, max.: 2 A
Output Delay with Resistive Load: "0" to "1", max.: 10 ms
"1" to "0", max.: 10 ms
Total Current of the Outputs (Per Group): Horizontal installation, up to 50 °C, max.: 10 A
Relay Outputs: Number of relay outputs: 16
Rated supply voltage of relay coil L+ (DC): 24 V
Number of Operating Cycles, Max.: Mechanically: 10 million
At rated load voltage: 100,000
Switching Capacity of Contacts: With inductive load, max.: 2 A
On lamp load, max.: 30 W with DC, 200 W with AC
With resistive load, max.: 2 A

Siemens Cable Length

Cable Length, Shielded, Max.: 500 m
Cable Length, Unshielded, Max.: 150 m

Siemens Environmental Conditions

Free Fall: Drop height, max. (in packaging): 0.3 m; five times, in dispatch package
Temperature: Permissible temperature range: -40 °C to +70 °C
Air Pressure acc. to IEC 60068-2-13: Permissible air pressure: 1080 to 660 hPa
Relative Humidity: Permissible range (without condensation) at 25 °C: 95%
Temperature - Operation: Permissible temperature range: -20 °C to +60 °C (horizontal mounting), -20 °C to 50 °C (vertical mounting), 95% humidity, non-condensing
Temperature Change: 5°C to 55°C, 3°C / minute

Siemens Dimensions

Width: 45 mm
Height: 100 mm
Depth: 75 mm

Siemens Weights

Weight, Approx.: 260 g