Technical Specifications:
Manufacturer:
Bently Nevada
Product No.:
136483-01
Condition:
In Stock
Product Type:
I/O Module
Product Origin:
USA
Weight:
460g
Shipping port:
Xiamen
Warranty:
12 months
The Bently Nevada 136483-01 is a highly reliable and accurate industrial automation product designed for signal processing in machinery protection systems. This isolated Input/Output (I/O) module specializes in handling current signals within the range of +4 to +20 milliamps (mA).
Specifications
Inputs
-
Input Options:
- +/-10 Vdc I/O: Accepts voltage signals between -10 and +10 Volts DC.
- 4-20 mA Barrier I/O: Handles 4-20 mA current loop signals with an internal barrier for added protection. It provides limited external transducer power (+24 Vdc, 250 mA max).
- 4-20 mA Isolated I/O: Accepts 4-20 mA current loop signals with electrical isolation to minimize noise interference.
-
Input Specifications:
- Voltage Compliance (4-20 mA Barrier I/O, 4-20mA out): Maximum voltage output of 13.66 V.
- Isolation (4-20 mA ISO I/O only): 500 Volts of isolation between input and output circuits.
-
Input Impedance:
- +/-10V I/O: 1 MΩ (Mega Ohm) impedance.
- 4-20 mA Barrier I/O & 4-20 mA Isolated I/O: 50 Ω (Ohm) impedance.
- Power Consumption: Typical power consumption of the monitor is 7.0 Watts.
- External Transducer Power (Internal Barrier I/O Only): Provides +24 Vdc with a current limit of 250 mA for powering external transducers.
Outputs
-
Front Panel LEDs:
- OK LED: Indicates proper operation of the monitor.
- TX/RX LED: Indicates communication activity with other modules in the 3500 rack.
- Bypass LED: Indicates when the process variable is in bypass mode.
Signal Conditioning
- Performed Internally: At +25°C (+77°F).
- Full-Scale Range: Configurable for each channel via the 3500 Configuration Software. No calibration required.
- Accuracy: Signal conditioning accuracy within ±0.33% of full-scale (typical) and ±1% maximum.
-
Full-Scale Range:
- Maximum of 20,000 units mapped across the input signal span.
- Minimum input signal span for voltage input is 2 Volts.
Alarms
-
User-Configurable Setpoints: Alert and Danger setpoints ranging from 0 to 100% of full-scale.
- Alarm Accuracy: Within 0.13% of the desired value.
-
Alarm Time Delays:
- Alert: 1 to 60 seconds in 1-second intervals.
- Danger: 1 to 60 seconds in 0.5-second intervals.
Proportional Values
- Process Variable Measurements: Used for machine monitoring.
- Outputs: Proportional values (current or voltage) in various configurable units.
Environmental Limits
-
Operating Temperature:
- -30°C to +65°C (-22°F to +149°F) with internal/external termination I/O module.
- 0°C to +65°C (+32°F to +149°F) with internal barrier I/O module (internal termination).
- Storage Temperature: -40°C to +85°C (-40°F to +185°F).
- Humidity: 95%, non-condensing.
I/O Module Dimensions and Weight
-
Without Barriers:
- Dimensions: 241.3 mm x 24.4 mm x 99.1 mm (9.50 in x 0.96 in x 3.90 in)
- Weight: 0.20 kg (0.44 lb)
-
With Barriers:
- Dimensions: 241.3 mm x 24.4 mm x 99.1 mm (9.50 in x 0.96 in x 3.90 in)
- Weight: 0.46 kg (1.01 lb)