Technical Specifications:
Overview
The Honeywell 900H02-0202 DC Digital Output module provides 16 outputs divided into 2 groups of 8 channels each, which are powered externally. Each group has a pair of screw terminals for +V and COM connections. The outputs are of the low side switching (current sinking) type. Overload protection is built into each output; when tripped, the power must be recycled to reset the module. Each channel on the module has a green LED state indicator to show when a digital output is ON. The module also features a green blinking status LED to indicate when it is being scanned, an amber blinking status LED to indicate when channels are forced, and a red status LED to indicate when module diagnostics exist.
Specifications
- Outputs per Module: 16 (current sinking, low side)
- Galvanic Isolation: 2 groups of 8 outputs
- Operating Voltage: 6.5 to 32 VDC (5.0 to 6.5 V @ <0.5A per channel)
- Output Type: Intelligent power switch (IPS)
- Peak Voltage: 34 VDC
- AC Frequency: N/A
- ON Voltage Drop: 0.3 VDC @ 1 A load
- Overload Protection: Electronic high current and high temperature limiting, resets after cycling field power
-
Maximum Load Current:
- 1 A per point, 8A max. per module, resistive load
- 0.5 A per point incandescent lamp load (5 mH max)
- Maximum Leakage Current: 0.15 mA @ 32 VDC
- Maximum Inrush Current: 4 A for 10 ms
- Minimum Load: 0.0 mA
-
Response Time:
- OFF to ON: 6 ms*
- ON to OFF: 6 ms*
- Fuses: Electronic limiting
-
Power Supply Loading:
- 5V; 340 mA
- 24V; 0 mA
*excluding controller scan time and transmission time from module to backplane
Features
- 16 outputs separated into 2 groups of 8 channels
- Externally powered groups with +V and COM connections
- Low side switching (current sinking) type outputs
- Built-in overload protection that requires power cycling to reset
- Green LED state indicators for each channel
- Green blinking status LED indicates scanning
- Amber blinking status LED indicates forced channels
- Red status LED indicates module diagnostics