HIMA HIMatrix F3 DIO 20/8 02 Safety-Related Remote I/O Module

HIMA HIMatrix F3 DIO 20/8 02 Safety-Related Remote I/O Module

Technical Specifications:

Manufacturer:
HIMA
Product No.:
F3DIO20/802
Condition:
In Stock
Product Type:
Remote I/O Module
Product Origin:
DE
Weight:
1400g
Shipping port:
Xiamen
Warranty:
12 months

Description

HIMA HIMATRIX safety-related F3 DIO 20/8 02 (F3DIO20/802) remote I/O is a compact system in a metal housing with 20 digital inputs and 8 digital outputs. . It features advanced fault detection and line control mechanisms to ensure high reliability and safety.

Technical Specifications

  • Digital Inputs:

    • Number: 20
    • Type: Configurable for various fault detection mechanisms (e.g., short-circuits, open-circuits)
    • Safety Standards: Compliant with Cat. 4 and PL e as per EN ISO 13849-1
  • Digital Outputs:

    • Number: 8
    • Usage: Can be used for line control in safety circuits (e.g., EMERGENCY STOP inputs)
  • Fault Detection:

    • Detects faults such as cross-circuits, invalid connections, earth faults, and open circuits.
    • Faults are indicated by the FAULT LED on the front panel.
    • Error codes are generated for precise fault identification.
  • Line Control:

    • Line control helps detect short-circuits or open-circuits.
    • Configuration for EMERGENCY STOP inputs according to safety standards.
    • Requires connection of digital outputs to corresponding digital inputs.

Functional Description

  1. Reaction to Faults:

    • If a fault is detected on a digital input, the module processes a low-level signal in accordance with the de-energized to trip principle.
    • The FAULT LED is activated.
    • User programs must consider the error codes to configure additional fault reactions.
  2. Line Control:

    • Used to detect short-circuits or open-circuits.
    • Configurable for remote I/O, especially for critical safety functions like EMERGENCY STOP.
    • Digital outputs DO 1 to DO 8 should be connected to digital inputs DI of the same system.
  3. Error Codes and Indicators:

    • Faults such as cross-circuits between parallel wires, invalid connections, earth faults, and open circuits trigger the FAULT LED and generate evaluable error codes.
    • The module ensures that in the event of a fault, the inputs are set to a low level to maintain safety.

Example Configuration

For implementing line control, connect the digital outputs to the digital inputs as follows:

  • DI 3 to DO 1
  • DI 1 to DO 2
  • DI 2 to DO 3
  • DI 4 to DO 4

Ensure that EMERGENCY STOP switches comply with EN 60947-5-1 and EN 60947-5-5 standards.

Safety Compliance

The F3 DIO 20/8 02 module is designed to meet stringent safety requirements, making it suitable for critical applications where reliability and fault detection are paramount.