Yokogawa SSC60D-S2512 Safety Control Unit

Yokogawa SSC60D-S2512 Safety Control Unit

Technical Specifications:

Manufacturer:
Yokogawa
Product No.:
SSC60D-S2512
Condition:
In Stock
Product Type:
Safety Control Unit
Product Origin:
99
Weight:
8500g
Shipping port:
Xiamen
Warranty:
12 months

Module Configuration

Component Description
Power Supply Module (SPW481, SPW482 or SPW484): 2 modules
Processor Module (S2CP471 or SCP461): 2 modules for dual-redundant configuration. (*1)
Memory Protection Application program is stored in flash memory. Processor module operation data is stored in NVRAM (nonvolatile memory).
Temperature Adaptability A fan unit is provided for high temperature use where the safety control units (SSC60S-F/SSC60D-F) ambient temperature exceeds 40 °C.
Communications Interface Vnet/IP interface: Dual-redundant. ESB bus interface: Dual-redundant.

Communication on Vnet/IP

Items Specifications
Communication Speed 100 Mbps, Full duplex
Connection UTP cable (CAT5e or higher), RJ45 connector
Interface 100Base-TX compliance
Max. Distance 100 m (distance between SSC60S/SSC60D and Layer 2 switch)

Connecting Safety Node Units

Component Description
Number of Safety Node Units Up to 13 safety node units can be connected using SEC402 ESB bus coupler module and adding CFS1350 Node Expansion Package. Up to 9 safety node units can be connected using SEC401 ESB bus coupler module.
Installation Requirements ESB bus coupler modules (SEC402/SEC401) should be mounted on 7-th and 8-th slots. ESB bus can be extended by Optical ESB bus repeater modules.

Number of I/O Modules Mounted

Items Specifications
Per Safety Control Unit Up to eight
Per SCS (with SEC402 and CFS1350) Up to 110
Per SCS (with SEC401) Up to 78

Power Requirements

Voltage Description
100 to 120 V AC, 50 or 60 Hz
220 to 240 V AC, 50 or 60 Hz
24 V DC

Power Consumption

Model 100 to 120 V AC 200 to 240 V AC 24 V DC
SSC60S-S/SSC60D-S 200 VA 230 VA 5.5 A
SSC60S-F/SSC60D-F 240 VA 290 VA 7.0 A

Battery

Component Part No. Replacement Period
S2CP471 S9450FE Three years under the average ambient temperature of 30 °C or less.
SCP461 S9185FA Three years under the average ambient temperature of 30 °C or less.

Weight

Model Weight
SSC60S-S Approximately 7.9 kg
SSC60S-F Approximately 13 kg
SSC60D-S Approximately 8.5 kg
SSC60D-F Approximately 13 kg

Suffix Codes

Code Description
-S Standard Type (-20 to 40 °C) (with ISA Standard G3 )
-F Wide range temperature (-20 to 70 °C) type (with Fan unit and ISA Standard G3)
 -2 Dual-redundant power supply
   -5 With no explosion protection
   -E With explosion protection
    -1 100-120 V AC power supply
    -2 220-240 V AC power supply
    -4 24 V DC power supply
       -1 CFS1300 Safety Control Function License (R3)
      -2 Without Safety Control Function License (R4.01 or later)

 

Dimension: 482.6 mm x 266 mm x 207 mm

NoteThe SCS is composed of a safety control unit, safety node units and an ESB bus connecting them.