REF615 ABB IEC Feeder Protection and Control Relay
REF615 ABB IEC Feeder Protection and Control Relay
Technical Specifications:
Manufacturer:
ABB
Product No.:
REF615
Condition:
In Stock
Product Type:
Feeder Protection and Control Relay
Product Origin:
Switzerland
Weight:
4100g
Shipping port:
Xiamen
Warranty:
12 months
Inputs and Outputs
Phase Current Inputs:
- IL1: X120-7, 8
- IL2: X120-9, 10
- IL3: X120-11, 12
Residual Current Inputs:
- Io: X120-13, 14 (configurations A, B, C, D, E, F, H, and J)
- Io: X130-1, 2 (configuration G)
Phase Voltage Inputs:
- U1: X130-11, 12
- U2: X130-13, 14
- U3: X130-15, 16
Residual Voltage Inputs:
- Uo: X120-5, 6 (configurations A and B)
- Uo: X130-17, 18 (configurations E, F, H, and J)
Operation Functionality
Optional Functions:
- Arc protection
- Autoreclosing
- Modbus TCP/IP or RTU/ASCII
- IEC 60870-5-103
- DNP3 TCP/IP or serial
- Admittance-based earth-fault (specific configurations)
- Watt-metric based earth-fault (specific configurations)
- Harmonics based earth-fault (specific configurations)
- Power quality functions (configuration J only)
Physical Hardware
The IED consists of two main parts: the plug-in unit and the case, with content depending on the ordered functionality.
Communication Protocols
- IEC 61850 with GOOSE messaging
- IEC 60870-5-103
- Modbus®
- DNP3
Product Version History
Version 1.0:
- Initial release
Version 1.1:
- IRIG-B, support for parallel protocols, enhanced CB interlocking functionality, TCS functionality in hardware enhanced, non-volatile memory added
Version 2.0:
- Support for DNP3 serial or TCP/IP, IEC 60870-5-103, voltage measurement and protection, new standard configurations, disturbance recorder upload via WHMI
Version 3.0:
- New configurations G and H, application configurability support, analog GOOSE support, large display with single line diagram, enhanced mechanical design
Version 4.0:
- New configuration J, dual fiber optic Ethernet communication option, additional logic blocks, watt-metric and harmonics-based earth-fault protection, power quality functions