Technical Specifications:

Manufacturer:
Bently Nevada
Product No.:
125672-02
Condition:
In Stock
Product Type:
Proximitor/Seismic Monitor
Product Origin:
USA
Weight:
720g
Shipping port:
Xiamen
Warranty:
12 months

Inputs

Signal: Accepts from 1 to 4 signal inputs.

Input Impedance:

  • Standard I/O: 10 kΩ
  • TMR I/O (Proximitor and Acceleration Inputs):
    • Bussed Transducer Configuration: 50 kΩ
    • Discrete Transducer Configuration: 150 kΩ

Power: Nominal consumption of 7.7 watts

Sensitivity:

Type Sensitivity
Radial Vibration 3.94 mV/µm (100 mV/mil) or 7.87 mV/µm (200 mV/mil)
Thrust 3.94 mV/µm (100 mV/mil) or 7.87 mV/µm (200 mV/mil)
Eccentricity 3.94 mV/µm (100 mV/mil) or 7.87 mV/µm (200 mV/mil)
Differential Expansion .394 mV/µm (10 mV/mil) or .787 mV/µm (20 mV/mil)
Acceleration 10 mV/(m/s²) (100 mV/g)
Velocity 20 mV/(mm/s) pk (500 mV/(in/s) pk), 5.8 mV/(mm/s) pk (145 mV/(in/s) pk), 4 mV/(mm/s) pk (100 mV/(in/s) pk)

Outputs

Front Panel LED’s:

  • OK LED: Indicates when the 3500/42 is operating properly.
  • TX/RX LED: Indicates when the 3500/42 is communicating with other modules in the 3500 rack.
  • Bypass LED: Indicates when the 3500/42 is in Bypass Mode.

Buffered Transducer Outputs: The front of each monitor has one coaxial connector for each channel. Each connector is short circuit protected.

Output Impedance: 550 Ω

Transducer Supply Values: -24 Vdc

Recorder: +4 to +20 mA. Values are proportional to monitor full scale. Individual recorder values are provided for each channel. Monitor operation is unaffected by short circuits on recorder outputs.

Voltage Compliance (current output): 0 to +12 Vdc range across load. Load resistance is 0 to 600 Ω.

Resolution: 0.3662 µA per bit

Accuracy: ±0.25 % error at room temperature, -0.66 to +0.70 % error over temperature range, updated rate 100 ms or less.

Signal Conditioning

Specified at +25° C (77° F)

Radial Vibration Frequency Response:

  • Direct Filter: User-programmable for 4 to 4,000 Hz or 1 to 600 Hz.
  • Gap Filter: -3 dB at .09 Hz.
  • Not 1X Filter: 60 cpm to 16 times running speed. Constant Q notch filter. Minimum rejection in stopband of –34.9 dB.
  • Smax: 0.125 to 16 times running speed. Constant Q Filter. Minimum rejection in stopband of -57.7 dB.
  • 1X & 2X Vector Filter: Valid for machine speeds of 60 to 60,000 cpm. Minimum rejection in stopband of -57.7 dB. Minimum Signal Amplitude for Phase measurement is 42.7 mV.

Accuracy:

  • Direct and Gap: Within ±0.33 % of full scale typical, ±1 % maximum.
  • 1X & 2X: Within ±0.33 % of full scale typical, ±1 % maximum.
  • Smax: Within ±5 % maximum.
  • Not 1X: ±3 % for machine speeds less than 30,000 cpm. ±8.5 % for machine speeds greater than 30,000 cpm.

Thrust and Differential Expansion

Frequency Response:

  • Direct Filter: -3 dB at 1.2 Hz.
  • Gap Filter: -3 dB at 0.41 Hz.

Accuracy: Within ±0.33 % of full scale typical, ±1 % maximum.

EIPP Monitor

Frequency Response:

  • Direct Filter: -3 dB at 15.6 Hz.
  • Gap Filter: -3 dB at 0.41 Hz.

Accuracy: Within ±0.33 % of full scale typical, ±1 % maximum.