Pular para as informações do produto
1 de 1

🚀 Produtos genuínos, vasto estoque, envio rápido!

ICS Triplex T9902 Replacement Output Fuse 10A

ICS Triplex T9902 Replacement Output Fuse 10A

Technical Specifications:

Manufacturer:
ICS Triplex
Product No.:
T9902
Condition:
In Stock
Product Type:
Replacement Output Fuse 10A
Product Origin:
USA
Weight:
316g
Shipping port:
Xiamen
Warranty:
12 months

Product Description:

The Rockwell Automation ICS Triplex T9902 is a surface mount fuse block designed for protecting electronic equipment's power and signal lines. This module includes a 10A, 125V fast-acting Littelfuse fuse, making it ideal for applications requiring rapid response to overcurrent conditions to protect circuits effectively.

Spares and Tools

T9902 Replacement Output Fuse

  • Product Description: Replacement output fuse 10A for T9851/2
  • Package Quantity: Pack of 20 (2 packs)

Technical Specifications:

  1. Manufacturer: Rockwell Automation
  2. Part Number: 154 010
  3. Fuse Block Type: SMF Omni-Block, Surface Mount
  4. Included Fuse:
    • Rating: 10 Amps, 125 Volts
    • Type: Fast Acting
    • Manufacturer: Littelfuse
  5. Compliance: UL 248-14

Recommended Fuse Types

The 10A fuses are fitted into the termination assembly and are specified as:

  • T9902: SMF Omni-Block, Surface Mount Fuse Block 154 010, with a 10A, 125V Fast Acting Fuse, Littelfuse.

Field Power Input Fuse Requirements

  • Rating: 5 Amps, 125 Volts
  • Type: Slow Blow
  • Compliance: Must comply with UL 248-14

Notes for Installation and Compliance:

  1. Alternative Power Supply Option:
    • Instead of fitting two 5A fuses, you can use Class 2 power supplies for the +24 VDC field voltage.
    • Class 2 Definition: According to the NEC, Class 2 power supplies provide less than 100 watts at 24V.
  2. Wiring Requirements:
    • Wire Gauge: Field power must be wired using 12 AWG wire.
  3. Power Supply Source:
    • Field power must be supplied from an isolating source.
  4. Line Monitoring Current Requirement:
    • The minimum current required for line monitoring is 20mA for a dual pair.
Ver informações completas