Honeywell FC-PUIO01 Safety Universal IO Module
Honeywell FC-PUIO01 Safety Universal IO Module
Technical Specifications:
Description
The Honeywell FC-PUIO01 Safety Universal I/O Module is a versatile component of the Honeywell Universal Marshalling Solution (UMS). It supports a wide range of signal types, including analog, digital, and HART, making it suitable for various safety-related applications. Rated for Safety Integrity Level (SIL) 3, the FC-PUIO01 ensures high reliability and safety in critical systems such as emergency shutdowns, fire alarms, gas detection, and burner management. With 32 channels and compatibility with 24VDC power supply, it offers enhanced flexibility and scalability in industrial environments.
Supported Modules
Safety Manager SC - FC-PUIO01 Safety Universal I/O Module
- FC-PUIO01: SC Safety Universal I/O Module, 24VDC, 32 Channels
Supported Hardware
This section details the hardware support restrictions and considerations.
2.1.1 Safety Manager SC Hardware
Safety Manager R210.2 supports the following Safety Manager SC Controller components:
-
FC-PDIO01: SC Safety DIO IOM, 24VDC, 32 Channels
- FC-TDIO11: SC IOTA PDIO Redundant
- FC-TDIO51: SC Safety FTA Knife, EOL, 24VDC, 16 Channels, Left
- FC-TDIO52: SC Safety FTA Knife, EOL, 24VDC, 16 Channels, Right
-
FC-PUIO01: SC Safety UIO IOM, 24VDC, 32 Channels
- FC-TUIO11: SC IOTA Safety UIO Redundant
- FC-TUIO51: SC FTA FC-PUIO01 Knife, EOL, 24VDC, 16 Channels, Left
- FC-TUIO52: SC FTA FC-PUIO01 Knife, EOL, 24VDC, 16 Channels, Right
Known Issues and Resolutions
Anomalies Resolved
The following table indicates anomalies resolved in the FC-PUIO01 firmware compared to Safety Manager R210.1:
PAR # | Abstract |
---|---|
SMSC-7792 | EC201 of FC-PUIO01 not displayed correctly |
SMSC-7794 | Both FC-PUIO01 modules status LED doesn't blink in Red when any one of CP power cycled |
SMSC-7882 | Analog input and output HART device-tree in Honeywell FDM may not be displayed correctly |
SMSC-7896 | The “Last status change” timestamp on Safety Builder Remote IO page is not correct for FC-PUIO01 |
SMSC-7957 | During FC-PUIO01 module replacement, open loops, short circuit and PV shifts observed on AI and DI_LM channels |
SMSC-7974 | FC-PUIO01 module reported EC95 on DO channel for Inductive Load during module replacement |
SMSC-7992 | FDM reports load failure due to parity error issue for FC-PUIO01 module |
SMSC-8014 | FC-PUIO01 LEDs not operational during startup |
SMSC-8043 | EC62 getting reported during redundant module turning on |
SMSC-8106 | FC-PUIO01 stops on redundant module power-up reported with error code EC30 |
Unresolved Anomalies
The following table indicates known issues that still exist for the FC-PUIO01 module:
PAR # | Abstract |
---|---|
SMSC-7164 | For systems with more than one IO module in the power supply group, FC-RUSIO-3224 and FC-PUIO01 may not localize earth faults on Digital Output channels. |
SMSC-7517 | Any single Ethernet cable fault on FC-PUIO01 sets both RIOLA and RIOLB system markers faulty for this module. |
SMSC-7778 | Nuisance EC228 can be observed during an online modification if the module lacks IO network cross-wiring between redundant CPs. |
SMSC-7134 | Intermittent Earth Fault on DI_LM channel in the same power supply group may report EC63 |
SMSC-7419 | Power cycle of FC-RUSIO-3224 with Analog Output channels and connected device may report EC58 |
SMSC-7709 | Power cycling FC-PDIO01 or FC-PUIO01 module during OLM may report EC102, EC95 for redundant modules |
SMSC-7779 | Adding AI with load on a spare channel of FC-PUIO01 may report EC62/EC63 after an application OLM. Fault reset clears EC62/EC63 |
1-C7PBD6H | Non-redundant FC-RUSIO-3224 or FC-PUIO01 AI and DI-LM channels may prevent the AI or DI-LM from reaching trip set point due to "current limiter" circuitry fault. |
Certification
- Standard: EN/ISO 13849-1
Configurations
- Safety Manager Controller or Safety Manager SC Controller connected with FC-RUSIO-3224, FC-PDIO01, or FC-PUIO01.
Descriptions & Conditions
To comply with the EN/ISO 13849-1 standard:
- Digital input signals allocated to FC-RUSIO-3224, FC-PDIO01, or FC-PUIO01 must be configured as Line Monitored Digital Input.
- Digital output signals allocated to these modules must have shielded field wiring.
Software Version Identification
Honeywell Components
Component | Version | CRC |
---|---|---|
Safety Universal IO (FC-PUIO01) | 210.2.0.234 | 0xFA4FD028 |
This structured format provides a comprehensive overview of the supported hardware, resolved issues, unresolved anomalies, certification compliance, and software version identification for the Honeywell Safety Manager Software R210.2.