NaN
/
de
-Infinity
🚀 Produtos genuínos, vasto estoque, envio rápido!
750-P5-G1-S1-HI-A20-R | GE Multilin 750 Feeder Protection System
750-P5-G1-S1-HI-A20-R | GE Multilin 750 Feeder Protection System
Technical Specifications:
Manufacturer:
GE
Product No.:
750-P5-G1-S1-HI-A20-R
Condition:
In Stock
Product Type:
750 Feeder Protection System
Product Origin:
USA
Weight:
0g
Shipping port:
Xiamen
Warranty:
12 months
The GE Multilin 750 Feeder Protection System is a digital relay designed for the primary protection and control of distribution feeders, as well as providing backup protection for bus, transformers, and transmission lines. It boasts a draw-out construction, making it easy to use and cost-effective throughout its product life cycle.
Key Benefits
- User-Friendly: Supported by industry-leading software tools.
- Accurate Metering: Built-in metering functions eliminate the need for auxiliary metering devices, reducing costs.
- Uptime Improvement: I/O monitoring improves the uptime of auxiliary equipment.
- Maintenance Cost Reduction: Features like IRIG-B time synchronization, event reports, waveform capture, and data logger reduce troubleshooting time and maintenance costs.
- Quick Replacement: Draw-out construction minimizes replacement time.
- Simplified Testing: Built-in simulation features.
- Cost-Effective Information Access: Supports industry protocols such as DNP & Modbus and includes an optional 10MB Ethernet port for system integration.
- Comprehensive Monitoring: Analog I/O and full metering, including demand and energy.
- Advanced Technology: Flash memory for field upgrades.
- Extended Life: Optional conformal coating for chemically corrosive and humid environments.
- Global Acceptance: Adheres to international codes and standards.
Technical Specifications
Protection Functions
- Phase/Neutral/Ground/Negative Sequence Time Overcurrent Protection: Pickup level of 0.05 to 20.00 in steps of 0.01 x CT, dropout level of 97 to 98% of pickup.
- Sensitive Ground Time Overcurrent Protection: Pickup level of 0.005 to 1.000 in steps of 0.001 x CT, dropout level of 97 to 98% of pickup.
- Phase/Neutral/Ground/Negative Sequence Instantaneous Overcurrent Protection: Pickup level of 0.05 to 20.00 in steps of 0.01 x CT, dropout level of 97 to 98% of pickup.
- Phase Directional Protection: MTA of 0 to 359° in steps of 1, angle accuracy of ±2°.
- Neutral Directional Protection: Polarized by voltage, current, or both, with angle accuracy of ±2°.
- Ground/Sensitive Ground Directional Protection: Polarized by voltage, current, or both, with angle accuracy of ±2°.
- Bus Undervoltage and Line Undervoltage Protection: Pickup level of 0.00 to 1.25 in steps of 0.01 x VT.
- Overvoltage Protection: Pickup level of 0.00 to 1.25 in steps of 0.01 x VT.
- Negative Sequence Voltage Protection: Pickup level of 0.00 to 1.25 in steps of 0.01 x VT.
- Underfrequency Protection: Pickup level of 20.00 to 65.00 Hz in steps of 0.01 Hz.
- Neutral Displacement Protection: Pickup level of 0.00 to 1.25 × VT in steps of 0.01.
- Reverse Power Protection: Pickup level of 0.015 to 0.600 × rated power.
- Breaker Failure Protection: Pickup level of 0.05 to 20.0 x CT in steps of 0.01.
Metering Functions
- Current Phasors: Phase A/B/C RMS current with ±0.5% accuracy of full scale.
- Voltage Phasors: Phase A-N (A-B), B-N (B-C), C-N (C-A) voltage with ±0.25% accuracy of full scale.
- Frequency Measurement: 16 to 65 Hz range with ±0.02 Hz accuracy.
- Symmetrical Components: Current and voltage level accuracy of ±1.5% and ±0.75% of full scale, respectively.
- Power Factor: Range of 0.00 Lag to 1.00 to 0.00 Lead with ±0.02 accuracy.
- Real Power: Range of -3000.0 to 3000.0 MW with ±1% accuracy.
- Reactive Power: Range of -3000.0 to 3000.0 Mvar with ±1% accuracy.
- Apparent Power: Range of -3000.0 to 3000.0 MVA with ±1% accuracy.
- Watt-Hours and Var-Hours: Range of -2.1 × 10^8 to 2.1 × 10^8 with ±2% accuracy.
Monitoring Functions
- Phase/Neutral Current: Pickup level of 0.05 to 20.00 × CT with ±100 ms timing accuracy.
- Power Factor: Pickup level of 0.50 lag to 0.50 lead with ±0.02 accuracy.
- Analog In Threshold and Rate: Pickup level from 0 to 65535 units and rate of -1000 to 1000 mA/hour with ±1% accuracy.
- Overfrequency: Pickup level of 20.01 to 65.00 Hz with ±0.02 Hz accuracy.
Event and Data Logging
- Event Recorder: Records up to 256 events with 1 ms time stamp.
- Waveform Capture: 4 currents, 3 voltages, 14 logic input states, and 8 output relays.
- Data Logger: 8 channels with various sample rates and trigger sources.
Inputs and Outputs
- Phase Current Input: 1 A or 5 A specified when ordering.
- Ground Current Input: 1 A or 5 A specified when ordering.
- Sensitive Ground Current Input: 1 A or 5 A specified when ordering.
- Voltage Input: 50 V to 240 V phase-neutral with less than 0.025 VA burden at 120 V.
- Logic Inputs: 14 contact and/or virtual, 6 virtual only.
- Analog Input: 0 – 1 mA, 0 – 5 mA, 0 – 10 mA, 0 – 20 mA, or 4 – 20 mA (programmable).
- Analog Outputs: 8 channels, specify output range when ordering.
Environmental and Approvals
- Operating Temperature: -40° C to +60° C.
- Storage Temperature: -40° C to +85° C.
- Humidity: Up to 95% (non-condensing) at 55°C.
- Pollution Degree: 2.
- IP Rating: IP40 (front), IP20 (back).
Communications
- Serial Ports: 300 – 19,200 baud, ModBus® RTU or DNP 3.0 protocol.
- Ethernet Port: 10BaseT, RJ45 Connector, ModBus® RTU over TCP/IP.
Power Supply
- Options: LO/HI specified when ordering.
- LO Range: DC = 20 to 60 V, AC = 20 to 48 V @ 48 – 62 Hz.
- HI Range: DC = 88 to 300 V, AC = 70 to 265 V @ 48 – 62 Hz.
- Power: 25 VA nominal, 35 VA maximum.
- Voltage Loss Hold-Up Time: 30 ms.
Tests and Approvals
- cULus: UL508, UL1058, C22.2.No 14.
- Type Tests: Include various standards like EN60255-5, EN50263, IEC 61000-4-18, and many more for dielectric strength, RF immunity, and environmental tests.
Ordering Information
-
Example: 750-P5-G1-S1-HI-A20-R
- Phase Current Inputs: P5 - 5 A phase current inputs
- Ground Current Inputs: G1 - 1 A zero sequence current inputs
- Sensitive Ground Current Inputs: S1 - 1 A sensitive ground current input
- Power Supply Options: HI - 88 – 300 VDC, 70 – 265 VAC @ 48 – 62 Hz
- Analog Outputs: A20 - Eight 4 – 20 mA analog outputs
- Breaker Status LED: R - Red breaker status LED
The GE Multilin 750 Feeder Protection System offers a comprehensive suite of protection, metering, and monitoring functions, supported by robust technical specifications and industry standards, ensuring reliable and efficient operation in various environments.