RLM02 ABB PROFIBUS Redundancy Link Module
RLM02 ABB PROFIBUS Redundancy Link Module
Technical Specifications:
Manufacturer:
ABB
Product No.:
RLM02
Condition:
In Stock
Product Type:
PROFIBUS Redundancy Link Module
Weight:
330g
Shipping port:
Xiamen
Warranty:
12 months
ABB RLM02 Redundancy Link Module for PROFIBUS DP/FMS
The ABB RLM02 Redundancy Link Module is designed to convert a non-redundant PROFIBUS line into two redundant RS485 lines, providing enhanced reliability and functionality for industrial communication systems. Below are the detailed specifications and features of the RLM02 module.
Benefits
- Conversion Capability: Converts one non-redundant PROFIBUS line into two redundant lines (A/B).
- Versatile Use: Applicable for PROFIBUS DP/FMS lines.
- Automatic Line Selection: Automatically selects the operational line.
- Wide Transmission Rate Range: Supports rates from 9.6 kbit/s to 12 Mbit/s.
- Communication Monitoring: Continuous monitoring of communication lines.
- Repeater Functionality: Regenerates signal shape and amplitude.
- Redundant Power Supply: Ensures uninterrupted power.
- Status and Error Display: LEDs indicate operational status and errors.
- Potential-Free Alarm Contact: Provides diagnostic capabilities.
- Easy Installation: Mounts on standard DIN rails.
Features
- Positioning: Can be placed directly after a master, before bus segments with multiple slaves, or before individual slaves.
- Redundant Coupler Compatibility: Connects directly to PROFIBUS stations with redundant couplers.
- Interface Assignment: Allows optional assignment of stations to line A or B.
- Capacity: Each interface can handle up to 31 PROFIBUS stations.
- Extended Line Length: Utilizes repeaters and media converters to extend PROFIBUS lines.
Function
- RS 485 Interfaces: Supports all transmission rates from 9.6 kbit/s to 12 Mbit/s as specified in IEC 61158-2.
- Repeater Functionality: Regenerates signal shape and amplitude.
- Monitoring: Monitors lines A, B, and M for activity and errors.
- Error Indication: Errors are indicated by front panel LEDs and potential-free alarm contacts.
- Power Supply Monitoring: Tests the presence of both power sources.
Technical Specifications
Parameter | Description |
---|---|
Baud Rate Settings | 9.6 kBd to 12 MBd |
Serial Interfaces | RS 485, 9-pin Sub-D connector, electrically isolated |
Power Supply | 24 VDC (+20 ... +33 V), 120 mA typically at 24 V, 3.6 W power loss, 8-pin terminal strip |
Operating Conditions | Temperature: 0 ... 55°C (operation), -30 ... 85°C (storage), Relative Humidity: Max 75% non-condensing |
Alarm Contact | Normally closed / Open in case of error, < 60 VDC, Max. 1 A |
Design |
Dimensions: 134 x 56 x 70 mm (H x W x D), Weight: 330 g, IP 20 protection |
Certification | UL-listed, CSA, CE, DNV GL (G3, B class) |
Adjustment and Indication
Description | Meaning | Remarks |
---|---|---|
Act | Bus activity on line A, B, or M | Yellow LED |
Err | Error on line A, B, or M | Red LED |
Power | Power supply status | Green LED |
Baud rate | Baud rate setting | Rotary switch (9.6 kBd ... 12 MBd) |