The Honeywell FC-PUIO01 Safety Universal I/O Module is a versatile component of the Honeywell Universal Marshalling Solution (UMS). It supports a wide range of signal types, including analog, digital, and HART, making it suitable for various safety-related applications. Rated for Safety Integrity Level (SIL) 3, the FC-PUIO01 ensures high reliability and safety in critical systems such as emergency shutdowns, fire alarms, gas detection, and burner management. With 32 channels and compatibility with 24VDC power supply, it offers enhanced flexibility and scalability in industrial environments.

Supported Modules

Safety Manager SC - FC-PUIO01 Safety Universal I/O Module

  • FC-PUIO01: SC Safety Universal I/O Module, 24VDC, 32 Channels

Supported Hardware

This section details the hardware support restrictions and considerations.

2.1.1 Safety Manager SC Hardware

Safety Manager R210.2 supports the following Safety Manager SC Controller components:

  • FC-PDIO01: SC Safety DIO IOM, 24VDC, 32 Channels
    • FC-TDIO11: SC IOTA PDIO Redundant
    • FC-TDIO51: SC Safety FTA Knife, EOL, 24VDC, 16 Channels, Left
    • FC-TDIO52: SC Safety FTA Knife, EOL, 24VDC, 16 Channels, Right
  • FC-PUIO01: SC Safety UIO IOM, 24VDC, 32 Channels
    • FC-TUIO11: SC IOTA Safety UIO Redundant
    • FC-TUIO51: SC FTA FC-PUIO01 Knife, EOL, 24VDC, 16 Channels, Left
    • FC-TUIO52: SC FTA FC-PUIO01 Knife, EOL, 24VDC, 16 Channels, Right

Known Issues and Resolutions

Anomalies Resolved

The following table indicates anomalies resolved in the FC-PUIO01 firmware compared to Safety Manager R210.1:

PAR # Abstract
SMSC-7792 EC201 of FC-PUIO01 not displayed correctly
SMSC-7794 Both FC-PUIO01 modules status LED doesn't blink in Red when any one of CP power cycled
SMSC-7882 Analog input and output HART device-tree in Honeywell FDM may not be displayed correctly
SMSC-7896 The “Last status change” timestamp on Safety Builder Remote IO page is not correct for FC-PUIO01
SMSC-7957 During FC-PUIO01 module replacement, open loops, short circuit and PV shifts observed on AI and DI_LM channels
SMSC-7974 FC-PUIO01 module reported EC95 on DO channel for Inductive Load during module replacement
SMSC-7992 FDM reports load failure due to parity error issue for FC-PUIO01 module
SMSC-8014 FC-PUIO01 LEDs not operational during startup
SMSC-8043 EC62 getting reported during redundant module turning on
SMSC-8106 FC-PUIO01 stops on redundant module power-up reported with error code EC30

Unresolved Anomalies

The following table indicates known issues that still exist for the FC-PUIO01 module:

PAR # Abstract
SMSC-7164 For systems with more than one IO module in the power supply group, FC-RUSIO-3224 and FC-PUIO01 may not localize earth faults on Digital Output channels.
SMSC-7517 Any single Ethernet cable fault on FC-PUIO01 sets both RIOLA and RIOLB system markers faulty for this module.
SMSC-7778 Nuisance EC228 can be observed during an online modification if the module lacks IO network cross-wiring between redundant CPs.
SMSC-7134 Intermittent Earth Fault on DI_LM channel in the same power supply group may report EC63
SMSC-7419 Power cycle of FC-RUSIO-3224 with Analog Output channels and connected device may report EC58
SMSC-7709 Power cycling FC-PDIO01 or FC-PUIO01 module during OLM may report EC102, EC95 for redundant modules
SMSC-7779 Adding AI with load on a spare channel of FC-PUIO01 may report EC62/EC63 after an application OLM. Fault reset clears EC62/EC63
1-C7PBD6H Non-redundant FC-RUSIO-3224 or FC-PUIO01 AI and DI-LM channels may prevent the AI or DI-LM from reaching trip set point due to "current limiter" circuitry fault.

Certification

  • Standard: EN/ISO 13849-1

Configurations

  • Safety Manager Controller or Safety Manager SC Controller connected with FC-RUSIO-3224, FC-PDIO01, or FC-PUIO01.

Descriptions & Conditions

To comply with the EN/ISO 13849-1 standard:

  1. Digital input signals allocated to FC-RUSIO-3224, FC-PDIO01, or FC-PUIO01 must be configured as Line Monitored Digital Input.
  2. Digital output signals allocated to these modules must have shielded field wiring.