Өнім туралы ақпаратқа өту
NaN ның -Infinity

🚀 Түпнұсқа өнімдер, үлкен инвентарь, жылдам жеткізу!

Honeywell 10106/2/1 Fail-safe Line-monitored Digital Input Module

Honeywell 10106/2/1 Fail-safe Line-monitored Digital Input Module

Technical Specifications:

Manufacturer:
Honeywell
Product No.:
10106/2/1
Condition:
In Stock
Product Type:
Digital Input Module
Product Origin:
USA
Weight:
400g
Shipping port:
Xiamen
Warranty:
12 months

10106/2/1 Fail-safe Line-monitored Digital Input Module with Earth Fault Monitor (16 Channels)

The 10106/2/1 digital input module is designed to provide reliable and safe monitoring of line-monitored loops or status signals derived from proximity switches. It includes advanced features such as earth fault monitoring and meets high safety requirements for critical applications.

Key Features:

  • Sixteen Channels: Supports line-monitored loops or status signals from proximity switches.
  • Earth Fault Monitoring: Detects any earth faults within the sixteen loops.
  • High Safety Standards: Meets DIN 19250 (AK5/6) and is suitable for SIL 3 applications according to IEC 61508.
  • Integrated Power Supply: On-board DC/DC converter provides power to connected field devices.
  • LED Indicators: Status of channels, loops, and module diagnostics are shown via front-panel LEDs.
  • Self-test Functionality: Controlled by the FSC system's central processor unit (CPU) for comprehensive diagnostics.

Technical Specifications:

General

  • Type Number: 10106/2/1 22101
  • Approvals: CE, UL, TÜV, FM
  • Safety Class: AK1-6
  • Software Versions: ≥ 510
  • Space Requirements: 4 TE, 3 HE (4 HP, 3U)

Power Requirements

  • 5 Vdc: 160 mA
  • 24 Vdc: 110 mA

Input Specifications (with 10106/A/1 Converter)

  • Number of Input Channels: 16
  • Input Type: According to DIN 19234 (NAMUR)
  • Switch Level: 1.4 to 1.9 mA
  • Hysteresis: 0.2 mA ± 0.05 mA
  • Field Wire Resistance: Max. 50 Ohm
  • 8 V Loop Supply:
    • Output Voltage: 7.9 to 8.7 V
    • Output Current: 170 mA (short-circuit proof)

Earth Connection Monitor

  • Input Resistance: Typically 0.5 MOhm (–40V < U < 40V)
  • Test Current: Typically 0.5 mA
  • Output Voltage: Typically 0.5 Vdc
  • Field Fault Voltage: Max. 250 Vac

Key Coding

  • Module Connector Code: Holes A5, C29
  • Rack Connector Code: Large Pins A5, C29

Field Device Compatibility

The types of field devices that can be connected to the channels of the 10106/2/1 module depend on the signal converter used:

Converter Type Type of Field Signal
10106/A/1 Dry contacts with line-monitoring function
10106/A/2 Dry contacts without line-monitoring function
10106/A/1 Proximity switches according to DIN 19234 (NAMUR)
10106/A/2 Pepperl+Fuchs (P+F) SN-series fail-safe proximity switches (ferrometal sensing)
10106/A/2 Pepperl+Fuchs (P+F) S1N-series fail-safe proximity switches (non-ferrometal sensing)

Notes:

  1. Using dry contacts with line-monitoring function requires a line terminator with a 10 kOhm resistor and a 1 kOhm resistor ±10%, 0.25 W.
  2. The combination of fail-safe sensors with the fail-safe input module 10106/2/1 meets the safety integrity requirements as laid down in IEC 61508.
  3. A maximum of 8 channels per 10106/A/2 converter may be used for dry contacts without a line-monitoring function.

Self-test Features

The self-test, controlled by the FSC system's central processor unit (CPU), includes:

  • Functional tests of various trip levels applied
  • Channel independence verification
  • Monitoring of supply voltage to input devices
  • Earth connection correctness verification
  • Correctness of supply voltages utilized

Related Tags :