10106/2/1 Fail-safe Line-monitored Digital Input Module with Earth Fault Monitor (16 Channels)
The 10106/2/1 digital input module is designed to provide reliable and safe monitoring of line-monitored loops or status signals derived from proximity switches. It includes advanced features such as earth fault monitoring and meets high safety requirements for critical applications.
Key Features:
- Sixteen Channels: Supports line-monitored loops or status signals from proximity switches.
- Earth Fault Monitoring: Detects any earth faults within the sixteen loops.
- High Safety Standards: Meets DIN 19250 (AK5/6) and is suitable for SIL 3 applications according to IEC 61508.
- Integrated Power Supply: On-board DC/DC converter provides power to connected field devices.
- LED Indicators: Status of channels, loops, and module diagnostics are shown via front-panel LEDs.
- Self-test Functionality: Controlled by the FSC system's central processor unit (CPU) for comprehensive diagnostics.
Technical Specifications:
General
- Type Number: 10106/2/1 22101
- Approvals: CE, UL, TÜV, FM
- Safety Class: AK1-6
- Software Versions: ≥ 510
- Space Requirements: 4 TE, 3 HE (4 HP, 3U)
Power Requirements
- 5 Vdc: 160 mA
- 24 Vdc: 110 mA
Input Specifications (with 10106/A/1 Converter)
- Number of Input Channels: 16
- Input Type: According to DIN 19234 (NAMUR)
- Switch Level: 1.4 to 1.9 mA
- Hysteresis: 0.2 mA ± 0.05 mA
- Field Wire Resistance: Max. 50 Ohm
-
8 V Loop Supply:
- Output Voltage: 7.9 to 8.7 V
- Output Current: 170 mA (short-circuit proof)
Earth Connection Monitor
- Input Resistance: Typically 0.5 MOhm (–40V < U < 40V)
- Test Current: Typically 0.5 mA
- Output Voltage: Typically 0.5 Vdc
- Field Fault Voltage: Max. 250 Vac
Key Coding
- Module Connector Code: Holes A5, C29
- Rack Connector Code: Large Pins A5, C29
Field Device Compatibility
The types of field devices that can be connected to the channels of the 10106/2/1 module depend on the signal converter used:
Converter Type | Type of Field Signal |
---|---|
10106/A/1 | Dry contacts with line-monitoring function |
10106/A/2 | Dry contacts without line-monitoring function |
10106/A/1 | Proximity switches according to DIN 19234 (NAMUR) |
10106/A/2 | Pepperl+Fuchs (P+F) SN-series fail-safe proximity switches (ferrometal sensing) |
10106/A/2 | Pepperl+Fuchs (P+F) S1N-series fail-safe proximity switches (non-ferrometal sensing) |
Notes:
- Using dry contacts with line-monitoring function requires a line terminator with a 10 kOhm resistor and a 1 kOhm resistor ±10%, 0.25 W.
- The combination of fail-safe sensors with the fail-safe input module 10106/2/1 meets the safety integrity requirements as laid down in IEC 61508.
- A maximum of 8 channels per 10106/A/2 converter may be used for dry contacts without a line-monitoring function.
Self-test Features
The self-test, controlled by the FSC system's central processor unit (CPU), includes:
- Functional tests of various trip levels applied
- Channel independence verification
- Monitoring of supply voltage to input devices
- Earth connection correctness verification
- Correctness of supply voltages utilized