GE IC695ALG616 PACSystems RX3i Analog Input Module

GE IC695ALG616 PACSystems RX3i Analog Input Module

Technical Specifications:

Manufacturer:
GE
Product No.:
IC695ALG616
Condition:
In Stock
Product Type:
Analog Input Module
Product Origin:
USA
Weight:
500g
Shipping port:
Xiamen
Warranty:
12 months

IC695ALG616 PACSystems RX3i Analog Input Module

Description

The IC695ALG616 is a Non-Isolated Differential Analog Current/Voltage Input module from the PACSystems RX3i series. It provides sixteen single-ended or eight differential input channels. This module is designed for industrial applications requiring precise analog input measurements and can be configured for various current and voltage ranges.

Features

  • Software Configurable: No need for module jumpers, simplifying configuration.
  • Full Autocalibration: Ensures accuracy at startup and during operation.
  • Error Checking: On-board error-checking capabilities.
  • Open-Circuit Detection: Available for all voltage and 4-20mA inputs.
  • Configurable Scaling and Offsets: Per-channel settings for tailored application needs.
  • Alarms: High, low, high-high, and low-low alarm detection and reporting per channel.
  • Fault Reporting: Module fault reporting supports diagnostic point fault contacts in the logic program.
  • Flash Memory: Allows for future upgrades.
  • Interrupts: Configurable for channel alarms and faults.
  • Terminal Block Detection: Detects insertion or removal of terminal blocks.

Technical Specifications

Parameter Specification
Input Ranges

Current: 0 to 20mA, 4 to 20mA, ±20mA

Voltage: ±10V, 0 to 10V, ±5V, 0 to 5V, 1 to 5V

Backplane Power Requirements 350 mA maximum @ 5.0V +5% / - 2.5%, 200 mA maximum @ 3.3V +5% / - 3%
Power Dissipation 4.25 W maximum
Thermal Derating No derating required
Resolution 24-bit ADC converted to Floating Point or Integer
Input Data Format Configurable as floating point IEEE 32-bit or 16-bit integer in a 32-bit field
Filter Options 8Hz, 12Hz, 16Hz, 40Hz, 200Hz, 500Hz
Input Impedance >100 kΩ voltage inputs
Current Input Resistance 249 Ω ±1%
Open Circuit Detection Time 1 second maximum
Overvoltage ±60 VDC continuous, maximum
Overcurrent ±28mA continuous, maximum
Noise Rejection Normal Mode: 85 dB @ 50/60 Hz with 8 Hz filter<br>Common Mode: 120 dB @ 50/60 Hz with 8 Hz filter
Crosstalk

-80 dB minimum (single-ended mode)

-80 dB minimum (differential mode, grounded common)

-60 dB minimum (differential mode, floating common)

Isolation Voltage 250 VAC continuous/1500 VAC for 1 minute (terminal block to backplane/chassis)

Installation in Hazardous Areas

  • Suitable for use in Class I, Division 2, Groups A, B, C, D, or non-hazardous areas.
  • Warning: Substitution of components may impair suitability for Class I, Division 2.
  • Warning: Turn off power before replacing or wiring modules in hazardous areas.
  • Warning: Do not connect or disconnect equipment unless the area is non-hazardous or power has been switched off.

LED Indicators

LED State Indicates
Module OK ON Green Module OK and configured
Green or Amber, blinking slowly Error
Green, blinking rapidly Module OK but not configured
OFF Module is defective or no backplane power present
Field Status ON Green No faults on any enabled channel and Terminal Block is present
ON Yellow Fault on at least one channel
OFF Terminal block not present or not fully seated
TB ON Red Terminal block not present or not fully seated
ON Green Terminal block is present
OFF No backplane power to module