Technical Specifications:
Manufacturer:
Bently Nevada
Product No.:
133442-01
Condition:
In Stock
Product Type:
I/O Module
Product Origin:
USA
Weight:
460g
Shipping port:
Xiamen
Warranty:
12 months
Specifications
Inputs
-
Signal:
- Each 3500/50M Tachometer Module accepts up to two transducer signals from proximity probe transducers or magnetic pickups.
- Input signal range: +10.0 V to -24.0 V (signals exceeding this range are limited internally by the module).
-
Input impedance:
- Standard: 20 kΩ
- TMR (Triple Modular Redundancy): 40 kΩ
- Internal Barrier: 7.15 kΩ
-
Power consumption: 5.8 watts, typical
-
Transducers:
- Accepts 1 to 2 proximity transducer signals
- Restrictions may apply to magnetic pickups (see Warning on page 2).
Outputs
-
Front Panel LEDs:
- OK LED: Indicates proper operation of the 3500/50M Tachometer Module.
- TX/RX LED: Indicates communication with other modules in the 3500 rack.
- Bypass LED: Indicates the module is in Bypass Mode.
-
Buffered Transducer Outputs:
- One coaxial connector per channel on the front of the module.
- Buffered outputs are available at the I/O module via Euro style connectors.
- Output Impedance: 550 Ω
-
Transducer Power Supply: 24 Vdc, 40 mA maximum per channel
-
Recorder Outputs:
- Current: +4 to +20 mA proportional to module full-scale range (rpm or rpm/min), provided individually for each channel.
- Monitor operation unaffected by short circuits on recorder outputs.
- Voltage Compliance (current output): 0 to +12 Vdc range across load, Load resistance 0 to 600 Ω
- Resolution: 0.3662 µA per bit ±0.25% error at room temperature, ±0.7% error over temperature range
- Update rate: Approximately 100 ms
Signal Conditioning
-
Specified at +25 ºC (+77 ºF)
-
Speed Input:
- Supports 1 to 255 events per revolution for Rotor Acceleration and Zero Speed channel types.
- Other channel types support 0.0039 to 255 events per revolution.
- Maximum full scale range: 99,999 rpm
- Maximum input frequency: 20 kHz
- Minimum input frequency:
- Proximity transducers: 0.0167 Hz (1 rpm for 1 event per revolution)
- Passive magnetic pickups: 3.3 Hz
-
RPM Accuracy:
- Less than 100 rpm: ± 0.1 rpm
- 100 to 10,000 rpm: ±1 rpm
- 10,000 to 99,999 rpm: ± 0.01% of true shaft speed
-
RPM/Min Accuracy: ± 20 rpm/min
Transducer Conditioning
-
Auto Threshold: For any input above 0.0167 Hz (1 rpm for 1 event/revolution). Minimum signal amplitude for triggering is 1 volt peak-to-peak.
-
Manual Threshold: User selectable from +9.5 Vdc to -23.5 Vdc. Minimum signal amplitude for triggering is 500 millivolts peak-to-peak.
-
Hysteresis: User selectable from 0.2 to 2.5 volts
Alarms
-
Alarm Setpoints:
- Alarm 1 levels can be set for each measured value.
- Alarm 2 setpoints can be set for any two measured values.
- Setpoints are adjustable from 0 to 100% of full scale for each measured value.
-
Alarm Time Delays:
- Alarm 1 Time Delay: 1 to 60 seconds in 1-second intervals
- Alarm 2 Time Delay: 1 to 60 seconds in 0.1-second intervals
Proportional Values
- Speed measurements used to monitor a machine. The module returns values like:
- Rotor Speed, Speed1, Speed Band, Peak Speed2, Rotor Speed 2, etc.
- Values for different channel types like Rotor Acceleration, Zero Speed, Reverse Rotation.
Physical
-
I/O Modules (internal barrier):
- Dimensions (Height x Width x Depth): 241.3 mm x 24.4 mm x 163.1 mm (9.50 in x 0.96 in x 6.42 in)
- Weight: 0.46 kg (1.01 lb)
Environmental Limits
-
Operating Temperature:
- With Internal/External Termination I/O Module: -30 ºC to +65 ºC (-22 ºF to +150 ºF)
- Storage Temperature: -40 ºC to +85 ºC (-40 ºF to +185 ºF)
- Humidity: 95% Non-condensing
Hazardous Area Approvals
- With I/O module ordering options without internal barriers:
- Ex nC [L] IIC, Class I, Division 2
- AEx nC IIC, Class I, Division 2, Groups A, B, C, D, T4 @ Ta = -20 °C to +65 °C (-4 °F to +150 °F) per drawing 149243
Compliance and Certifications
-
EMC Standards:
- EN 61000-6-2 Immunity for Industrial Environments
- EN 61000-6-4 Emissions for Industrial Environments
- EN 55011/CISPR 11 ISM Equipment
-
European Community Directives:
- EMC Directive 2004/108/EC
- Electrical Safety Standards: EN 6110-1
- Low Voltage Directive 2006/95/EC
Ordering Considerations
- External Termination Blocks cannot be used with Internal Termination I/O modules.
- When ordering I/O Modules with External Terminations, order External Termination Blocks and cables separately.
- Use Bussed External Termination Blocks with TMR I/O modules only.