1
/
ның
1
🚀 Түпнұсқа өнімдер, үлкен инвентарь, жылдам жеткізу!
07 MK 92 ABB GJR5253300R1161 Communication Module
07 MK 92 ABB GJR5253300R1161 Communication Module
Technical Specifications:
Manufacturer:
ABB
Product No.:
07-MK-92
Condition:
In Stock
Product Type:
Communication Module
Product Origin:
Switzerland
Weight:
450g
Shipping port:
Xiamen
Warranty:
12 months
Main Features of the Communication Module
-
4 serial interfaces:
- 2 serial interfaces, optionally configurable in accordance with EIA RS-232 or EIA RS-422 or EIA RS-485 (COM3, COM4)
- 2 interfaces in accordance with EIA RS-232 (COM5, COM6)
- Freely programmable with a comprehensive function library
- Communication with AC31 basic unit via connection elements
- Configurable LEDs for diagnosis
- Programming and testing on a PC via COM3
- Saving applications in a Flash EPROM
Processing of the serial interfaces and the networking interface is provided for in an applications program. Programming is in the standard language ”C”. The exchange of data between the serial communication module and the AC31 basic unit is realized by connection elements in the basic unit.
Technical Data
Specification | Details |
---|---|
Number of serial interfaces | 4 |
Number of parallel interfaces | 1 networking interface for connecting to the Advant Controller 31 basic unit |
Built-in application software memory | Flash EPROM 128 kbytes |
Diagnosis | 4 configurable LEDs: LED1...4 (controlled by the application program) |
Operating and error displays | 3 LEDs: RUN, ERR, Supply |
Conductor cross section for the removable terminals | Max. 2.5 mm² |
Supply Voltage for 07 MK 92 R1161
Specification | Details |
---|---|
Rated supply voltage | 24 V DC |
Power dissipation | Typ. 2.5 W |
Max. current consumption with rated voltage | 210 mA |
Max. current consumption with supply voltage 30 V | 170 mA |
Protection against reversed terminal connection | Yes (only when units with electrically isolated interfaces are connected to COM5/COM6) |
Connection of Serial Interfaces COM3, COM4
Specification | Details |
---|---|
Interface standard | EIA RS-232 or EIA RS-422 or EIA RS-485 |
Programming | With 907 MK 92 via IBM-PC (or compatible) |
Man-machine communication | Yes, e.g., with an operating station |
Electrical isolation | Yes, interfaces with respect to each other and with respect to the rest of the unit (also see Figure 5) |
Potential differences | To prevent earthing potential differences between the 07 MK 92 and the peripheral units connected to COM3 and COM4, the latter are supplied from the switch-gear cabinet mains socket (also see earthing connections in Figure 5). |
Connection of Serial Interfaces COM5, COM6
Specification | Details |
---|---|
Interface standard | EIA RS-232 |
Man-machine communication | Yes, e.g., with an operating station |
Electrical isolation | None |
LED Displays
LED Type | Color | Function |
---|---|---|
Supply voltage present (Supply) | 1 green LED | Indicates presence of supply voltage |
Fatal or serious error occurred (ERR) | 1 red LED | Indicates a fatal or serious error |
Application program processing running (RUN) | 1 green LED | Indicates that the application program is running |
Configurable LEDs for diagnosis | LED1...LED4 | 4 yellow LEDs configurable by the application program |
Mechanical Data
Specification | Details |
---|---|
Mounting | On DIN rail in accordance with DIN EN 50022–35, 15 mm deep. The DIN rail is located in the middle between the upper and lower edges of the module. |
Fastening | By screws using 4 M4 screws |
Dimensions (Width x Height x Depth) | 140 x 120 x 85 mm |
Wiring method | By removable terminal blocks with screw-type terminals, max. 2.5 mm² |
Weight | 450 g |