07 AI 91 ABB 07AI91 GJR5251600R0202 Advant OCS Analog I/O module
07 AI 91 ABB 07AI91 GJR5251600R0202 Advant OCS Analog I/O module
Technical Specifications:
Description
The ABB 07AI91 is an analog input module designed for use in the CS31 system bus. It features 8 analog input channels that can be configured in pairs to connect various temperature or voltage sensors. This module supports sensors such as ±10 V, ±5 V, ±500 mV, ±50 mV, 4...20 mA (with external 250 Ω resistor), Pt100/Pt1000 with linearization, and thermocouples types J, K, and S with linearization. The 07AI91 module is designed to be used with electrically isolated sensors only. Configuration of input channels and module addressing is performed via DIL switches.
Features
- Configurable Channels: The 8 analog input channels can be configured in pairs for different types of sensors.
- Sensor Compatibility: Supports a wide range of sensors including voltage, current (with external resistor), Pt100/Pt1000, and thermocouples.
- Electrical Isolation: Ensures safe operation with electrically isolated sensors and CS31 system bus interface.
- Self-Calibration: Includes diagnostic functions that perform self-calibration for all channels.
- LED Indicators: Equipped with 17 LEDs for channel selection, diagnosis, and error messages.
- Simple Configuration: Input channels and module addresses are configured using DIL switches under the right housing cover.
Specifications
- Number of Channels: 8 analog input channels (configurable in pairs)
- Operating Temperature: 0...55 °C
- Supply Voltage: 24 V DC
- Current Consumption: Max. 0.15 A
- Power Dissipation: Max. 3 W
- Protection Against Reversed Polarity: Yes
- Conductor Cross Section: Max. 2.5 mm² for removable connectors
- Electrical Isolation: From CS31 system bus interface
- Line Frequency Suppression: Configurable for 50 Hz, 60 Hz, or none
- Input Delay: 0 (no RC combination)
- Line Frequency Hum Suppression: 20.0 ms at 50-Hz suppression, 16.7 ms at 60-Hz suppression
- Permissible Input Overvoltage: Max. ±30 V
-
Updating Period per Channel:
- With suppression 50/60 Hz: Typical 100 ms
- Without suppression: Typical 30 ms
- Using thermocouples with suppression 50/60 Hz: Typical 150 ms
Voltage Inputs
- Input Resistance: > 1 MΩ
- Measuring Ranges: ±10 V, ±5 V, ±500 mV, ±50 mV
- Resolution: 12 bit + sign
- Total Error: < ±0.5 % of full scale
Current Inputs
- Current Range: 0...20 mA / 4...20 mA
- Required External Shunt: 250 Ω
- Total Error: < ±0.5 % of full scale ± tolerance of the shunt
Pt100/Pt1000 Inputs
- Evaluation Range with Linearization: -50°C...+400°C
-
Resistance of Sensors:
- Pt100: 80.31 Ω...247.04 Ω
- Pt1000: 803.1 Ω...2470.4 Ω
- Resolution: 12 bit + sign (1 LSB = 0.1°C)
- Permissible Total Line Resistance: Max. 50 Ω per sensor (in 4-wire configuration)
-
Evaluation Error:
- Pt100: +/- 0.5 % of full scale
- Pt1000: +/- 1.0 % of full scale
Dimensions and Weight
- Dimensions: 140x120x85mm
- Weight: Approximately 0.59 kg
The ABB 07AI91 analog input module offers versatile sensor compatibility, reliable performance, and ease of use, making it a valuable component for industrial automation systems.