Technical Specifications:

Manufacturer:
ABB
Product No.:
RDCU-12C
Condition:
In Stock
Product Type:
Drive Control Unit
Product Origin:
USA
Weight:
600g
Shipping port:
Xiamen
Warranty:
12 months

General:

  • Mounting

    • Onto 35 × 7.5 mm DIN mounting rail

  • Housing materials

    • Zinc-plated steel (base); ABS/PC (cover)

Connector types:

  • X20 (Constant voltage output): 2-pole detachable screw terminal block
  • X21 (Analogue I/O): Four 3-pole detachable screw-type terminal blocks
  • X22 (Digital inputs): One 3-pole and two 4-pole detachable screw-type terminal blocks
  • X23 (24 VDC output): 2-pole detachable screw-type terminal block
  • X25-X27 (Relay outputs): Three 3-pole detachable screw-type terminal blocks
  • X31 (Slot 1), X32 (Slot 2): 38-pin header (female), pitch 2 mm
  • X33 (DDCS): 20-pin header (female), pitch 2.54 mm
  • X34 (24 VDC power input): 3-pole detachable screw-type terminal block
  • X39 (Control panel): 12-pin header (male), pitch 2.54 mm
  • V57, V68 (PPCS link): Fibre optic transmitter/receiver (10 MBd)

Constant voltage output (X20, X21:1):

  • Voltage: +10 VDC, 0, -10 VDC ±0.5% (Full scale range) at 25 °C (77 °F)
  • Temperature coefficient: ±100 ppm/°C (±56 ppm/°F) max.
  • Maximum load: 10 mA
  • Applicable potentiometer: 1 to 10 kohm

Analogue inputs (X21):

  • Two programmable differential current inputs: (0 mA / 4 mA … 20 mA, Rin = 100 ohm)
  • One programmable differential voltage input: (-10 V / 0 V / 2 V … +10 V, Rin = 200 kohm)
  • Isolation test voltage: 500 VAC, 1 min
  • Resolution: 0.025% (12 bit) for -10 V … +10 V, 0.5% (11 bit) for 0 … +10 V and 0…20 mA
  • Inaccuracy: ±0.5% (Full scale range) at 25 °C, Temperature coefficient: ±100 ppm/°C max.

Analogue outputs (X21):

  • Two programmable current outputs: 0 (4) … 20 mA, RL < 700 ohm
  • Resolution: 0.1% (10 bit)
  • Inaccuracy: ±1% (Full scale range) at 25 °C, Temperature coefficient: ±200 ppm/°C (±111 ppm/°F) max.

Digital inputs (X22):

  • Six programmable digital inputs: (common ground: 24 VDC, -15% … +20%)
  • Thermistor input: 5 mA, < 1.5 kohm "1" (normal temperature), > 4 kohm "0" (high temperature)
  • Isolation test voltage: 500 VAC, 1 min
  • Logical thresholds: < 8 VDC "0", > 12 VDC "1"
  • Input current: DI1 to DI5: 10 mA; DI6: 5 mA
  • Filtering time constant: 1 ms

24 VDC power output (X23):

  • Voltage: 24 VDC ±10%, short-circuit proof
  • Maximum output current: 250 mA (without any optional modules inserted)

Relay outputs (X25, X26, X27):

  • Three programmable relay outputs
  • Switching capacity: 8 A at 24 VDC or 250 VAC; 0.4 A at 120 VDC
  • Isolation test voltage: 4 kVAC, 1 min

24 VDC power input (X34):

  • Voltage: 24 VDC ±10%
  • Typical current consumption (without option modules): 250 mA
  • Maximum current consumption: 1200 mA (with option modules inserted)

Ambient conditions:

  • Operating temperature: +0 … +60 °C (32…140 °F)
  • Storage temperature: -40 … +70 °C (-40 … +158 °F)