GE IC695ALG616 PACSystems RX3i Analog Input Module
GE IC695ALG616 PACSystems RX3i Analog Input Module
Technical Specifications:
Manufacturer:
GE
Product No.:
IC695ALG616
Condition:
In Stock
Product Type:
Analog Input Module
Product Origin:
USA
Weight:
500g
Shipping port:
Xiamen
Warranty:
12 months
IC695ALG616 PACSystems RX3i Analog Input Module
Description
The IC695ALG616 is a Non-Isolated Differential Analog Current/Voltage Input module from the PACSystems RX3i series. It provides sixteen single-ended or eight differential input channels. This module is designed for industrial applications requiring precise analog input measurements and can be configured for various current and voltage ranges.
Features
- Software Configurable: No need for module jumpers, simplifying configuration.
- Full Autocalibration: Ensures accuracy at startup and during operation.
- Error Checking: On-board error-checking capabilities.
- Open-Circuit Detection: Available for all voltage and 4-20mA inputs.
- Configurable Scaling and Offsets: Per-channel settings for tailored application needs.
- Alarms: High, low, high-high, and low-low alarm detection and reporting per channel.
- Fault Reporting: Module fault reporting supports diagnostic point fault contacts in the logic program.
- Flash Memory: Allows for future upgrades.
- Interrupts: Configurable for channel alarms and faults.
- Terminal Block Detection: Detects insertion or removal of terminal blocks.
Technical Specifications
Parameter | Specification |
---|---|
Input Ranges |
Current: 0 to 20mA, 4 to 20mA, ±20mA Voltage: ±10V, 0 to 10V, ±5V, 0 to 5V, 1 to 5V |
Backplane Power Requirements | 350 mA maximum @ 5.0V +5% / - 2.5%, 200 mA maximum @ 3.3V +5% / - 3% |
Power Dissipation | 4.25 W maximum |
Thermal Derating | No derating required |
Resolution | 24-bit ADC converted to Floating Point or Integer |
Input Data Format | Configurable as floating point IEEE 32-bit or 16-bit integer in a 32-bit field |
Filter Options | 8Hz, 12Hz, 16Hz, 40Hz, 200Hz, 500Hz |
Input Impedance | >100 kΩ voltage inputs |
Current Input Resistance | 249 Ω ±1% |
Open Circuit Detection Time | 1 second maximum |
Overvoltage | ±60 VDC continuous, maximum |
Overcurrent | ±28mA continuous, maximum |
Noise Rejection | Normal Mode: 85 dB @ 50/60 Hz with 8 Hz filter<br>Common Mode: 120 dB @ 50/60 Hz with 8 Hz filter |
Crosstalk |
-80 dB minimum (single-ended mode) -80 dB minimum (differential mode, grounded common) -60 dB minimum (differential mode, floating common) |
Isolation Voltage | 250 VAC continuous/1500 VAC for 1 minute (terminal block to backplane/chassis) |
Installation in Hazardous Areas
- Suitable for use in Class I, Division 2, Groups A, B, C, D, or non-hazardous areas.
- Warning: Substitution of components may impair suitability for Class I, Division 2.
- Warning: Turn off power before replacing or wiring modules in hazardous areas.
- Warning: Do not connect or disconnect equipment unless the area is non-hazardous or power has been switched off.
LED Indicators
LED | State | Indicates |
---|---|---|
Module OK | ON Green | Module OK and configured |
Green or Amber, blinking slowly | Error | |
Green, blinking rapidly | Module OK but not configured | |
OFF | Module is defective or no backplane power present | |
Field Status | ON Green | No faults on any enabled channel and Terminal Block is present |
ON Yellow | Fault on at least one channel | |
OFF | Terminal block not present or not fully seated | |
TB | ON Red | Terminal block not present or not fully seated |
ON Green | Terminal block is present | |
OFF | No backplane power to module |