900A16-0103 Honeywell Analog Input High Level 16 Channel
900A16-0103 Honeywell Analog Input High Level 16 Channel
Technical Specifications:
Analog Input High Level, 16 Channel (900A16-0103)
The High-Level Analog Input module supports up to 16 user-configurable inputs on a per-point basis for voltage or current. It provides point-to-point isolation and back-plane isolation. The modules perform analog-to-digital conversion in synchronization with CPU control execution, eliminating data interchange latency. All analog input modules are processed in parallel, eliminating scan time increases as modules are added. A green blinking status LED on the module indicates when the module is being scanned, and a red status LED indicates when module or channel diagnostics exist.
High Level Analog Input Specifications
Item | Specification |
---|---|
Inputs per Module | 16 (isolated) |
Input Types | V, mA |
Input Impedance | >1 megohm for volts and 250 ohms for mA inputs |
Galvanic Input Isolation | 400 VDC point to point, solid state switching; 1K VDC to logic |
Noise Rejection |
Series Mode >31dB Common Mode >90dB at 120VAC |
Over-range Limit | +/- 10% for linear ranges (volts) |
Accuracy | Factory configured accuracy = ± 0.1 % of range |
Reference Conditions |
Temperature = 25 °C ± 3 °C (77 °F ± 5 °F) Humidity = 45 % to 55 % RH non-condensing Line voltage = Nominal ± 1 % Source resistance = 0 ohm Series mode and common mode = 0 V Frequency = Nominal ± 1 % |
Temp. Effect on Accuracy | ±0.01% of full scale per degree Celsius maximum |
A/D Converter | One per module |
A/D Resolution | ±15 Bits |
Update Rate | 100ms (Analog to Digital Converter per module) |
Long Term Stability | 0.1% per year |
Calibration |
Data is stored in non-volatile memory Redundant Factory Calibration |
Diagnostics | Monitoring of Factory Calibration, 24 VDC supply, and configuration |
Channel Configuration Data | Stored in non-volatile memory |
High Level Analog Input Reference Accuracy
Input Type | Range | Reference Accuracy |
---|---|---|
Milliamperes | 4 to 20 mAdc | ± 0.15% F.S. (mA) |
0 to 20 mAdc | ± 0.15% F.S. (mA) |