🚀 Orijinal məhsullar, geniş inventar, sürətli çatdırılma!
Triconex Invensys 3624 24VDC Digital Output Module
Triconex Invensys 3624 24VDC Digital Output Module
Technical Specifications:
Triconex Invensys 3624 16-Point Supervised Digital Output Modules
Description
Designed for the most critical control programs, the supervised digital output (SDO) modules are ideal for systems where outputs remain in a single state for extended periods, sometimes years. Each SDO module receives output signals from the main processors on three channels. The signals are voted upon by a fully fault-tolerant quadruplicated output switch with power transistors, producing a single voted output signal passed to the field termination.
The SDO modules feature voltage and current loopback circuitry, along with sophisticated online diagnostics, verifying the operation of each output switch, the field circuit, and the presence of a load. This comprehensive fault coverage does not interfere with the output signal. The "supervised" designation indicates the module's ability to detect potential field problems, including:
- Loss of power or blown fuse
- Open or missing load
- Field short causing unintended load energization
- Shorted load in the de-energized state
Field voltage detection failure on any output point triggers the power alarm indicator, while load presence detection failure triggers the load alarm indicator. All SDO modules support hot-spare modules and require a separate external termination panel (ETP) with a cable interface to the Tricon backplane.
Key Features
- Critical Control Programs: Ideal for systems with extended output states.
- Fault-Tolerant Design: Fully fault-tolerant quadruplicated output switch ensures reliable operation.
- Comprehensive Diagnostics: Voltage and current loopback circuitry with online diagnostics.
- Field Supervision: Detects various field faults, including power loss, open or missing load, field short, and shorted load.
- Hot-Spare Support: All modules support hot-spare replacements.
- External Termination Panel: Requires a separate ETP with a cable interface to the Tricon backplane.
Models: 3624
Feature | Model 3624 |
---|---|
Nominal Voltage | 24 VDC |
Type | TMR, Supervised |
Output Signals | 16, commoned |
Voltage Range | 16-30 VDC |
Maximum Voltage | 36 VDC |
Voltage Drop | < 1.5 VDC, typical |
Power Module Load | < 10 watts |
Current Ratings, Maximum | 0.7A per point, 4.8A surge per 10 ms |
Minimum Required Load | 30 mA |
Load Leakage | 4 mA maximum |
Fuses (on Field Termination) | n/a—self-protecting |
Point Isolation | 1500 VDC |
Diagnostic Indicators | 1 per point, PASS, FAULT, ACTIVE, POWER, LOAD (1 per point) |
Color Code | Turquoise Green |
Related Tags :
Paylaşın
- Seçim seçimi səhifənin tam yenilənməsi ilə nəticələnir.