Overview: The 10310/2/1 module is an Earth Leakage Detector (ELD) designed for monitoring and detecting earth faults in 24 V DC systems. It features a manual self-test function and earth connection monitoring for ensuring system integrity and safety.
Features:
- Earth Leakage Detection: Capable of monitoring earth faults in 24 V DC, 48 V DC, 60 V DC, or 110 V DC systems.
- Earth Connection Monitoring: Offers continuous or intermittent monitoring of the earth connection.
- Self-Test Functionality: Can be manually activated or triggered via input signals (Rst24, Rst110).
- Reset Options: Supports manual resetting or high-level signal application to Rst24 or Rst110 inputs.
- Test Capability: Tests the module and earth connection using a 1.5 kOhm resistor or a resistor connected to the Earth2 pin.
- LED Indicator: Displays the selected connection frequency when operating in intermittent mode.
Technical Specifications:
Power:
- Supply Voltage: 24 V DC (max. 30 V DC)
- Supply Current: Max. 60 mA
Input Voltage:
-
Rst24: 18 to 70 V DC
- Input Current: 1.1 mA at 24 V DC
-
Rst110: 40 to 130 V DC
- Input Current: 2.5 mA at 110 V DC
Earth:
- Earth Voltage: -12 V DC (no earth fault)
- Earth Fault Threshold: -30 to +125 V DC
-
Max. Earth Current:
- 5.5 mA (± 1 mA)
- 25.0 mA (± 5 mA)
Output Contact:
- Max. Output Voltage: 115 V DC
- Max. Output Current: 2 A
Relay Contacts:
- Initial Contact Resistance: 30 mOhm
- Max. Current: 5A
- Max. Switched Voltage: 250 V DC / 250 V AC
- Max. Switched Load: 100 W / 1000 VA
- Expected Electrical Life: 100,000 switch operations
- Expected Mechanical Life: 200,000,000 switch operations
Installation:
- Module Code: Holes A5, A11
- Rack Code: Large pins A5, A11
Weight:
- Weight: 0.2 kg
The 10310/2/1 ELD offers robust earth fault detection and monitoring capabilities, providing critical safety functions for various DC systems.