FC-TSDO-0824C Honeywell Safe Digital Output FTA

In stock
Manufacturer:
Honeywell
Product No.:
FC-TSDO-0824C
Condition:
In Stock
Product Type:
Safe Digital Output FTA
Product Origin:
USA
Weight:
300g
Shipping port:
Xiamen
Warranty:
12 months

UBEST – Trusted Global Automation Parts Supplier

We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.

About Us | Contact

TSDO-0824C Safe Digital Output FTA (24 V DC, 8 Channels)

The TSDO-0824C module is a conformal coated safe digital output Field Termination Assembly (FTA) designed for hazardous environments. It interfaces between the safe digital output module SDO-0824 and external field wiring, ensuring safe connections in Class I, Division 2 hazardous locations.

Key Features:

  • Output Channels: Provides eight current-limited safe digital outputs to the field, each capable of supplying 110 mA (2.5 Watt at 24 V DC).
  • Conformal Coating: Complies with type A coating requirements specified in IEC 60664-3 for Pollution Degree 1 environments.
  • Mounting: Features a universal snap-in provision for standard DIN EN rails.
  • Termination: Equipped with screw terminals for easy field wiring connections.

Technical Specifications:

General:

  • Type Number: FC-TSDO-0824C
  • Approvals: CE, TUV, UL, CSA, FM

Power:

  • Number of Channels: 8
  • Maximum Voltage: 36 V DC (IEC 1010, overvoltage category 3)
  • Power Requirements: 5 mA per channel (plus output load)

Output:

  • Output Current Limit: > 110 mA
  • Max. Output Load: 2.5 Watt (at 24 V DC)
  • Voltage Drop: < 1.5 V DC at 110 mA
  • Off Current: < 0.1 mA

Physical:

  • Module Dimensions: 110 × 70 × 48 mm (4.32 × 2.76 × 1.89 in)
  • DIN EN Rails: TS32 / TS35 × 7.5
  • Used Rail Length: 111 mm (4.36 in)

Termination:

  • Screw Terminals:
    • Max. Wire Diameter: 2.5 mm² (AWG 14)
    • Strip Length: 7 mm
    • Tightening Torque: 0.5 Nm

Field Signal Specifications:

HYDROGEN (Group A & B):

  • Max. Loop Inductance: 3.0 mH
  • Max. Loop Capacitance: 0.2 µF

NON-HYDROGEN (Group C & D):

  • Max. Loop Inductance: 12 mH
  • Max. Loop Capacitance: 5 µF