🚀 Genuine products, vast inventory, swift shipping!
F 6217 | HIMA F6217 Safety-Related 4-Fold Analog input Module
F 6217 | HIMA F6217 Safety-Related 4-Fold Analog input Module
Technical Specifications:
Manufacturer:
HIMA
Product No.:
F6217
Condition:
In Stock
Product Type:
Analog input Module
Product Origin:
DE
Weight:
1200g
Shipping port:
Xiamen
Warranty:
12 months
Description:
The HIMA F 6214 is a safety-related, 4-fold analog input module designed for use with transmitters in two-wire technique. It is capable of handling current inputs (0...20 mA) and voltage inputs (0...1/5/10 V) and features safety isolation. The module has a resolution of 12 bits and conforms to requirement class AK 1 ... 6.
Technical Specifications:
-
Input Types:
- Current Input: 0...20 mA
- Voltage Input: 0...1 V, 0...5 V, 0...10 V
- Transmitter Supply: 25 V ... 20 V, 0 ... 22 mA
-
Input Voltage:
- 0...1.06 V (approximately 6% overflow)
- Digital values: 0 mV = 0, 1 V = 3840
- Input Resistance: 1 MOhm
- Time Constant Input Filter: Approximately 10 ms
- Short Circuit Current: 25 mA
- Load Impedance: Maximum 900 Ohm
- Scan Time: Maximum 100 ms for 4 channels
- Basic Error: 0.2% at 25 °C
- Operating Error: 0.3% at 0...+60 °C
- Electric Strength: 250 V against GND
-
Power Requirements:
- 5 V DC: 150 mA
- 24 V DC: 250 mA
- Space Requirement: 4 TE (Terminals)
- Termination: All unused channels must be terminated to ensure correct operation.
-
Safety Testing:
- Automatic testing during operation including tests for linearity of the AD-converter, cross-talk between input channels, function of input filters, and transmitter supply voltage.
Additional Information:
-
Cable Specifications:
- Cable Type: LiYCY
- Dimensions: 12 x 0.25 mm², screened, l = 120 mm, q = 2.5 mm²
- Channel Connection Color Coding: Specific colors assigned for each channel.
- Flat Pin Plug: 2.8 x 0.8 mm² and 6.3 x 0.8 mm to be connected to the earth bar under the slot.
-
Planning Notes:
- Termination of all unused analog inputs is necessary for the correct operation of internal test routines.
- Specific resistor values and part numbers are provided for various configurations and termination requirements.
Related Tags :
Share
- Choosing a selection results in a full page refresh.
- Opens in a new window.