F 6217 | HIMA F6217 Safety-Related 4-Fold Analog input Module

F 6217 | HIMA F6217 Safety-Related 4-Fold Analog input Module

Technical Specifications:

Manufacturer:
HIMA
Product No.:
F6217
Condition:
In Stock
Product Type:
Analog input Module
Product Origin:
DE
Weight:
1200g
Shipping port:
Xiamen
Warranty:
12 months

Description:

The HIMA F 6214 is a safety-related, 4-fold analog input module designed for use with transmitters in two-wire technique. It is capable of handling current inputs (0...20 mA) and voltage inputs (0...1/5/10 V) and features safety isolation. The module has a resolution of 12 bits and conforms to requirement class AK 1 ... 6.

Technical Specifications:

  • Input Types:
    • Current Input: 0...20 mA
    • Voltage Input: 0...1 V, 0...5 V, 0...10 V
    • Transmitter Supply: 25 V ... 20 V, 0 ... 22 mA
  • Input Voltage:
    • 0...1.06 V (approximately 6% overflow)
    • Digital values: 0 mV = 0, 1 V = 3840
  • Input Resistance: 1 MOhm
  • Time Constant Input Filter: Approximately 10 ms
  • Short Circuit Current: 25 mA
  • Load Impedance: Maximum 900 Ohm
  • Scan Time: Maximum 100 ms for 4 channels
  • Basic Error: 0.2% at 25 °C
  • Operating Error: 0.3% at 0...+60 °C
  • Electric Strength: 250 V against GND
  • Power Requirements:
    • 5 V DC: 150 mA
    • 24 V DC: 250 mA
  • Space Requirement: 4 TE (Terminals)
  • Termination: All unused channels must be terminated to ensure correct operation.
  • Safety Testing:
    • Automatic testing during operation including tests for linearity of the AD-converter, cross-talk between input channels, function of input filters, and transmitter supply voltage.

Additional Information:

  • Cable Specifications:

    • Cable Type: LiYCY
    • Dimensions: 12 x 0.25 mm², screened, l = 120 mm, q = 2.5 mm²
    • Channel Connection Color Coding: Specific colors assigned for each channel.
    • Flat Pin Plug: 2.8 x 0.8 mm² and 6.3 x 0.8 mm to be connected to the earth bar under the slot.
  • Planning Notes:

    • Termination of all unused analog inputs is necessary for the correct operation of internal test routines.
    • Specific resistor values and part numbers are provided for various configurations and termination requirements.