8C-PAOH51 Honeywell Analog Output Module with HART

In stock
Manufacturer:
Honeywell
Product No.:
8C-PAOH51
Condition:
In Stock
Product Type:
Analog Output Module
Product Origin:
USA
Weight:
300g
Shipping port:
Xiamen
Warranty:
12 months

UBEST – Trusted Global Automation Parts Supplier

We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.

About Us | Contact

8C-PAOH51 Analog Output with HART Function

The Analog Output (AO) Module delivers high-level constant current to actuators and recording/indicating devices.

Notable Features

  • Extensive self diagnostics
  • Optional redundancy
  • HART-capable, multivariable instruments
  • Safe-state (FAILOPT) behaviors configurable on a per channel basis
  • Non-incendive output (No external user supplied power)

Safe-state Behavior (FAILOPT)

The Series 8 AO module supports the FAILOPT parameter on a per channel basis. The user can configure each channel to either HOLD LAST VALUE, or SHED to a SAFE VALUE. The output will always go to zero, the safe state, if the IOM device electronics fail.

Open-wire Detection

This Series 8 IO function can detect and annunciate open field wire with a Channel Soft Failure indication.

Detail Specifications – Analog Output with HART

Parameter Specification
Input / Output Model

8C-PAOH51 - Analog Output with HART, Coated

8U-PAOH51 - Analog Output with HART, Uncoated

IOTA Models

8C-TAOX51 Non-Redundant, Coated 6”

8U-TAOX51 Non-Redundant, Uncoated 6”

8C-TAOX61 Redundant, Coated 12”

8U-TAOX61 Redundant, Uncoated 12”

Output Type 4-20 mA
Output Channels 16
Output Ripple < 100 mV peak-to-peak at power line freq, across 250 Ω load
Resolution ± 0.05% of Full Scale
Calibrated Accuracy ± 0.35% of Full Scale (25°C) including linearity
Directly Settable Output Current Range 0 mA, 2.9 mA to 21.1 mA
Maximum Open Circuit Voltage 22 V
Response Time (DAC input code to output) Settles to within 1% of final value within 80 ms
Gap (0 mA) of Output to Field on Switchover 10 ms maximum (applies to Redundancy only)