Technical Specifications

Parameter Specification
Input 1-phase AC
Supply Voltage ● 1 at AC Rated value 120 V
● 2 at AC Rated value 230 V
● Note Automatic range selection
Input Voltage ● 1 at AC 85 ... 132 V
● 2 at AC 176 ... 264 V
Wide-Range Input No
Overvoltage Resistance 2.3 × Vin rated, 1.3 ms
Mains Buffering at Iout Rated Min. 20 ms; at Vin = 120/230 V
Rated Line Frequency ● 1 50 Hz
● 2 60 Hz
● Rated line range 47 ... 63 Hz
Input Current ● at rated input voltage 120 V 7.5 A
● at rated input voltage 230 V 3.5 A
Switch-On Current Limiting (+25 °C) Max. 11 A
Output Controlled, isolated DC voltage
Rated Voltage Vout DC 24 V
Total Tolerance, Static ± 3 %
Static Mains Compensation Approx. 0.5 %
Static Load Balancing Approx. 1 %
Residual Ripple Peak-Peak, Max. 150 mV
Spikes Peak-Peak, Max. (Bandwidth: 20 MHz) 240 mV
Adjustment Range 24 ... 28 V
Output Voltage Adjustable Yes
Output Voltage Setting Via potentiometer; max. 480 W
Status Display Green LED for 24 V OK
Signaling Relay contact (NO contact, rating 50 V DC/0.3 A) for "24 V OK"
On/Off Behavior No overshoot of Vout (soft start)
Startup Delay, Max. 1.5 s
Voltage Rise, Typ. 50 ms
Voltage Increase Time of the Output Voltage Maximum 500 ms
Rated Current Value Iout Rated 20 A
Current Range 0 ... 20 A
● Note 24 A up to +45°C; +60 ... +70 °C: Derating 5%/K
Supplied Active Power Typical 480 W
Short-Term Overload Current ● On short-circuiting during the start-up typical 35 A
● At short-circuit during operation typical 35 A
Duration of Overloading Capability for Excess Current ● On short-circuiting during the start-up 100 ms
● At short-circuit during operation 100 ms
Parallel Switching for Enhanced Performance Yes
Numbers of Parallel Switchable Units for Enhanced Performance 2
Efficiency Approx. 90 % at Vout rated, Iout rated
Power Loss at Vout Rated, Iout Rated Approx. 53 W
Closed-Loop Control Dynamic mains compensation (Vin rated ±15 %), max. 1 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. 3 %
Setting time maximum 10 ms
Operating Data Ambient temperature
● During operation 0 ... 70 °C — Note with natural convection
● During transport -40 ... +85 °C
● During storage -40 ... +85 °C
Humidity class according to EN 60721 Climate class 3K3, no condensation
Mechanics Connection technology screw-type terminals
Width of the enclosure 115 mm
Height of the enclosure 145 mm
Depth of the enclosure 150 mm
Required spacing
● Top 50 mm
● Bottom 50 mm
● Left 0 mm
● Right 0 mm
Weight, approx. 2.4 kg