Honeywell FC-TSHART-1620M Safe Analog Input FTA
UBEST – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
TSHART-1620m Safe Analog Input FTA with HART Interface (16 Channels)
The TSHART-1620m module acts as the interface between field components (sensors, etc.) and the safe high-density analog input module SAI-1620m in Safety Manager. Featuring a HART interface, it supports signals from Class I, Division 2 Hazardous Locations. With sixteen analog input channels, it is suitable for both safety-related and non-safety-related applications. These channels connect via a system interconnection cable (SICC-0001/Lx) to a redundant pair of SAI-1620m modules.
Main Functions:
- Signal Conversion: Linear direct conversion of 0(4)-20 mA DC field signals to the signal levels of the SAI-1620m module.
- HART Compatibility: Enables connection to HART multiplex units from MTL or Pepperl+Fuchs (P+F).
- Power Distribution: Provides power supply distribution to each transmitter with voltage-current limitation, compliant with Hazardous Area Class I Division 2.
- Monitoring: Enables monitoring of the external power connected to the FTA module.
Technical Data:
General:
- Type Numbers: FS-TSHART-1620m, FC-TSHART-1620m
- Approvals: CE, TUV, UL, CSA, FM
Input:
- Number of Input Channels: 16 (2 groups of 8 with common 0 V)
- Power Requirements: 30 V DC external, 3 mA (without input loop loads)
- Input Current: 0-25 mA
- Input Resistance: 250 Ω (± 1%)
Output:
-
To Passive Transmitters (Vext):
- Output Resistance: 270 Ω (± 5%)
- Igniting Current per Channel: < 120 mA at 30 V DC
-
To SAI-1620m Module:
- Output Voltage: 0-4 V DC
- Accuracy: 0.10%
-
To HART Multiplex Unit:
- Output Voltage: Max. 5 V peak-peak
- Series Impedance: > 100 nF
Fuse:
- Fuse Rating: 315 mA
- Fuse Dimensions: 5x20 mm
- Voltage Rating AC: 125 V
- Maximum Output Current per Fuse: 220 mA
- Manufacturer: SOC
- Manufacturer PN: MQ2 315 mA
Physical:
- Module Dimensions: 250 × 70 × 60 mm (9.84 × 2.76 × 2.36 in)
- DIN EN Rails: TS32 / TS35 × 7.5
- Used Rail Length: 251 mm (9.87 in)
Termination:
-
Screw Terminals:
- Max. Wire Size: 2.5 mm² (AWG 14)
- Strip Length: 7 mm (0.28 in)
- Tightening Torque: 0.5 Nm (0.37 ft-lb)
Field Signal Specifications for Non-Incendive Field Circuits, Class I Division 2:
HYDROGEN (Group A & B):
- Max. Loop Inductance: 6 mH
- Max. Loop Capacitance: 0.25 µF
NON-HYDROGEN (Group C & D):
- Max. Loop Inductance: 20 mH
- Max. Loop Capacitance: 5 µF
The TSHART-1620m is a reliable FTA module for safe analog input applications with HART interface, designed for easy installation on DIN EN rails and secure connection via screw terminals. It ensures precise signal conversion and effective power distribution, suitable for hazardous environments.