Manufacturer:
Honeywell
Product No.:
10310/2/1
Condition:
In Stock
Product Type:
Earth Leakage Detector
Product Origin:
USA
Weight:
200g
Shipping port:
Xiamen
Warranty:
12 months

UBEST – Trusted Global Automation Parts Supplier

We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.

About Us | Contact

10310/2/1 Earth Leakage Detector (ELD)

Overview: The 10310/2/1 module is an Earth Leakage Detector (ELD) designed for monitoring and detecting earth faults in 24 V DC systems. It features a manual self-test function and earth connection monitoring for ensuring system integrity and safety.

Features:

  • Earth Leakage Detection: Capable of monitoring earth faults in 24 V DC, 48 V DC, 60 V DC, or 110 V DC systems.
  • Earth Connection Monitoring: Offers continuous or intermittent monitoring of the earth connection.
  • Self-Test Functionality: Can be manually activated or triggered via input signals (Rst24, Rst110).
  • Reset Options: Supports manual resetting or high-level signal application to Rst24 or Rst110 inputs.
  • Test Capability: Tests the module and earth connection using a 1.5 kOhm resistor or a resistor connected to the Earth2 pin.
  • LED Indicator: Displays the selected connection frequency when operating in intermittent mode.

Technical Specifications:

Power:

  • Supply Voltage: 24 V DC (max. 30 V DC)
  • Supply Current: Max. 60 mA

Input Voltage:

  • Rst24: 18 to 70 V DC
    • Input Current: 1.1 mA at 24 V DC
  • Rst110: 40 to 130 V DC
    • Input Current: 2.5 mA at 110 V DC

Earth:

  • Earth Voltage: -12 V DC (no earth fault)
  • Earth Fault Threshold: -30 to +125 V DC
  • Max. Earth Current:
    • 5.5 mA (± 1 mA)
    • 25.0 mA (± 5 mA)

Output Contact:

  • Max. Output Voltage: 115 V DC
  • Max. Output Current: 2 A

Relay Contacts:

  • Initial Contact Resistance: 30 mOhm
  • Max. Current: 5A
  • Max. Switched Voltage: 250 V DC / 250 V AC
  • Max. Switched Load: 100 W / 1000 VA
  • Expected Electrical Life: 100,000 switch operations
  • Expected Mechanical Life: 200,000,000 switch operations

Installation:

  • Module Code: Holes A5, A11
  • Rack Code: Large pins A5, A11

Weight:

  • Weight: 0.2 kg

The 10310/2/1 ELD offers robust earth fault detection and monitoring capabilities, providing critical safety functions for various DC systems.