8C-PAIH54 Analog Input with HART - Differential
Description
The 8C-PAIH54 51307070-275 Analog Input Module with HART capability accepts high-level current or voltage inputs from transmitters and sensing devices, supporting both single-ended and differential configurations.
Notable Features
- Extensive self-diagnostics
- Optional redundancy
- Supports Single Ended / Differential Inputs
- HART-capable for multivariable instruments and multiple modems
- Fast loop scan
Detailed Specification - Analog Input with HART (8C-PAIH54)
Parameter | Specification |
---|---|
Input / Output Module | 8C-PAIH54 - Analog Input with HART (16), Coated |
IOTA Modules |
8C-TAIDA1 Non Redundant, Coated 9”; 8C-TAIDB1 Redundant, Coated 12’’ |
Input Type | Voltage, Current (2-wire or self-powered transmitters), Single ended or Differential inputs |
Input Channels | 16 Channels (All 16 Single Ended or Differential type) |
A/D Converter Resolution | 16 bits |
Input Range | 0 to 5 V, 1 to 5 V, 0.4 to 2 V, 4-20 mA (through 250 Ω) |
Voltage Rating | 24 VDC |
Module Current Rating | 310 mA |
Common Mode Rejection Ratio, dc to 60 Hz | 70 dB (500 Ω source imbalance) |
Common Mode Voltage, dc to 60 Hz | -6 to +5 V peak |
Normal Mode Rejection Ratio, at 60 Hz | 19 dB |
Normal Mode Filter Response | Single-pole RC, -3 dB @ 6.5 Hz |
Crosstalk, dc to 60 Hz (channel-to-channel) | -60 dB |
Input Impedance (voltage inputs) | > 10 M Ω powered |
Maximum Normal Mode Input | ± 30 Volts |
Input Scan Rate | 50 ms |
Hardware Accuracy (@ CMV = 0 V) |
± 0.075% of full-scale (23.5°C ± 2°C) ± 0.15% of full-scale (0 to 60°C) |
Module Removal and Insertion Under Power | Supported |
Transmitter Field Power Conditioning | Individually Protected Current Limiting Circuits, No fuse required |