GE IC200PNS002 VersaMax PROFINET Scanner Module
GE IC200PNS002 VersaMax PROFINET Scanner Module
Technical Specifications:
Description
The VersaMax PROFINET Scanner (PNS) module interfaces a remote node of VersaMax modules to a PROFINET IO-Controller. The PROFINET Scanner scans the modules in its node, retrieving input data and providing output data, and publishes input data on the PROFINET Network at the configured production rate. The PNS manages PROFINET communication and module configuration between an IO-Controller and modules within the remote node. If network communications are lost, the PNS manages I/O states according to the individual module configurations.
Features
- Supports redundant power supplies. Use of the second power supply is optional.
- Supports “hot swap” of a redundant power supply that is de-energized.
- Standard PROFINET alarm and diagnostics reporting.
- Supports configuration using Classless Inter-Domain Routing (CIDR) with subnetting and supernetting.
- Each network interface module can be connected into a daisy-chain/line, star, or ring (redundant media) topology.
- Supports Media Redundancy Protocol (MRP) client mode operation.
- Can be upgraded in the field; supports firmware updates via USB port.
- Provides Maintenance Mode to allow servicing of the remote node while maintaining network connections. (Requires firmware version 1.10 or later.)
Specifications
PROFINET Support
- PROFINET Version 2.2 Class A IO-Device
Power Consumption
- IC200PNS002: 1.10A at 5VDC
Module Dimensions
- Height: 132mm (5.2 inches)
- Width: 134mm (5.28 inches)
Carrier Required
- No. Carrier is integrated into the module.
Operating Temperature Range
- 0 to 60°C surrounding air temperature without a fan
Number of Port Connectors
- IC200PNS002: Two SC-Duplex
USB Connector (for firmware upgrades)
- One Micro-B connector. USB 2.0 compliant running at Full-speed (12 MHz).
PNS Status and Control Bits
- 32 input status bits and 32 output control bits
I/O Data Update on the PROFINET LAN
- Configurable: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms, and 512ms
Number of IP Addresses
- One. Supports Classless Inter-Domain Routing (CIDR).
Number of MAC Addresses
- Three. One per external port and one internal. External MAC addresses are only used for specialized Ethernet protocols such as MRP or LLDP.
I/O Station Maximum Limits
- Number of I/O Modules per station: Eight
- I/O data per station: 2880 bytes total
- 1440 bytes of input data
- 1440 bytes of output data